Belimo UK24BAC Manual de datos técnicos - Página 16

Navegue en línea o descargue pdf Manual de datos técnicos para Pasarela Belimo UK24BAC. Belimo UK24BAC 20 páginas. Belimo gateway mp to bacnet ms/tp

UK24BAC

Version overview

Firmware V1.10
Firmware V1.09
Firmware V1.08
Firmware V1.07
Firmware V1.06
Firmware V1.03
16 / 20
Belimo Gateway MP to BACnet MS/TP
New functions/modifications:
The disengaged gear is represented on the objects ACT_VALUE_[n] and ABS_POS_[n]
using the Status-Flags (OVERRIDDEN) and now also in the property Reliability.
Changes of the Status-Flags generate COV-Notifications (if enabled)
Handling of network priorities corrected
Increased MS/TP communication quality on MS/TP
Known issues:
 –
New functions/modifications:
The disengaged gear is represented on the objects ACT_VALUE_[n] and ABS_POS_[n]
using the Status-Flags (OVERRIDDEN)
Known issues:
 –
New functions/modifications:
 OFFSET_DEV_ID Setting adjusted to 0...4'194'056 (2
 New functional profile "MPL actuator" supported (e.g. CQ24A-MPL)
 Integrated sensor conversion   °C for PT1000, NI1000 and NTC5K
 Nominal volumetric flow (VAV/EPIV) as BACnet Object available
 MP addressing function reworked
Known issues:
 –
New functions/modifications:
 WritePropertyMultiple service supported
 Feedback values are rounded
 Unconfirmed-COV-Notification for Multi-state Value fixed (wrong datatype)
 PropertyIdentifier for COV_Increment fixed (wrong ID)
 Sending of malformed packets fixed (in relation with WhoIs requests)
 Instability on high baudrate (76.8k) resolved
Known issues:
 –
New functions/modifications:
 Unsolicited-COV-Reporting for volumetric flow added
 Engineering units (position/volumetric flow/pressure) is updated (if supported by actuator)
 Instability on high bus load resolved
Known issues:
 WritePropertyMultiple service not supported
New functions/modifications:
 Property State_Text changed to BACnetARRAY
 Property Description in SUM_FAULT object with bit field (internal state) completed
 Unsolicited-COV-Reporting supported (see known issues)
 Absolute position ABS_POS_[n] calculated
Known issues:
 WritePropertyMultiple service not supported
 Engineering units (position and volumetric flow) not for all actuator types updated
 Unsolicited-COV-Reporting for volumetric flow not supported
T9-UK24BAC • en • v1.9 • 06.2018 • Subject to changes