Belimo UK24BAC Manual de datos técnicos - Página 3

Navegue en línea o descargue pdf Manual de datos técnicos para Pasarela Belimo UK24BAC. Belimo UK24BAC 20 páginas. Belimo gateway mp to bacnet ms/tp

UK24BAC
Gateway MP BACnet MS/TP. MP-bus-
capable Belimo actuators can be
connected on the MP-Bus side.
 Interface MP – BACnet MS/TP
 Connection of MP/MPL/MFT(2)
actuators and BF-TopLine
actuators to BACnet MS/TP
 Up to 8 actuators and sensors can
be connected

Technical data

Electrical data
Functional data
Installation / Dimension / Weight
www.belimo.com
Belimo Gateway MP to BACnet MS/TP
Nominal voltage
Power supply range
For wire sizing
Connection
Supported actuators
Quantity of actuators
Communication with actuators
Maximum signal conductor lengths MP
BACnet
Safety
Protection class
EMC
Ambient temperature
Mounting
Dimensions
Weight
T9-UK24BAC • en • v1.9 • 06.2018 • Subject to changes
AC 24 V, 50/60 Hz / DC 24 V
AC/DC 21.6...26.4 V
3 VA / 1.8 W
BACnet MS/TP
Plug-screw terminal, 3-pin
Supply
Plug-screw terminal, 2-pin
MP-Bus
Plug-screw terminal, 3-pin
(All terminals suitable for 2 x 1.5 mm
Tool
RJ12
MP/MPL/MFT(2), BF-TopLine
max. 8 pcs.
Belimo MP-Bus, Master-Slave, 1200 Bd
Dependent on the number of connected actuators,
actuator type, type of supply and signal conductor
cross-section
For details see page 5
Device Profile
Application Specific Controller (B-ASC)
Medium
MS/TP (RS-485) master, galvanically isolated
Number of nodes
max. 32 (without repeater)
Baud rates
9'600, 19'200, 38'400, 76'800 Bd,
adjustable via DIP switch
Termination
120
, adjustable via DIP switch
Polarisation
510
, adjustable via DIP switch
III Safety extra-low voltage
CE pursuant to 2004/108/EC
0...+40 °C
Control cabinet installation,
can be snapped onto top hat rail 35 mm
see page 7
ca. 100 g
2
)