UK24MOD
Operation elements
Operation, behaviour
Setting the Modbus address
8 / 20
Belimo Gateway MP to Modbus RTU
Legend
Addressing of the
MP nodes
Display of the active
MP nodes
The illustration shows the operation elements of the device with the front cover open.
The Modbus address is set in binary form with the 8 DIP switches under the front cover. The
valid address range is 1-247. Values outside of this range will be interpreted as either 1 or 247,
respectively.
T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes
+
-
+
-
┴
┴
~
~
Setting
Baud rate
Power LED
MP-Bus LED
Modbus LED
Setting
Modbus address
┴
D- D+
Setting
Terminator,
Polarisation,
Parity