Apollo 65 Series Manual de instalación - Página 2

Navegue en línea o descargue pdf Manual de instalación para Sensores de seguridad Apollo 65 Series. Apollo 65 Series 4 páginas. Base mounted marine uv flame detector

Apollo 65 Series Manual de instalación
Sensor window contamination
It is important to keep the sensor window clean and checks should be carried out at
regular intervals–determined locally according to the type and degree of contamination
encountered– to ensure optimal performance of the fl ame detector.
It is recommended that the fl ame detector be disabled when the window is being
cleaned.
Applications for Marine UV Flame Detectors
Flame detectors are used when detection is required to be unaffected by convection cur-
rents, draughts or wind; tolerant of fumes, vapours, responsive to a fl ame up to 25m away
and fast reacting.
Typical applications examples are:
• engine room
• factory
• garage
• hospital
• printing
• warehouse
Applications and locations to avoid:
• outdoors
• open windows and doorways
• electric sparks, arcs and welding
• UV lamps
• radiation sources
• prolonged ambient temperatures above 60°C
• exposure to water and ice
• gathering of dust or oil fi lms on sensor window
• fl ood or spot lighting falling directly on UV optics
• obstructions to fi eld of view
www.acornfiresecurity.com
2
www.acornfiresecurity.com
10. Inform all appropriate personnel on completion of the maintenance work and if
necessary record this work.
Technical Data
Supply voltage
Quiescent current
Alarm voltage
Normal alarm current
Remote output characteristics
Alarm indicator
Design alarm load
Hold voltage
Holding current
Minimum voltage required
to illuminate indicators
Alarm reset voltage
Alarm reset time
Operating Range
Sensitivity Switch Options
Field of view
Spectral response
Operating temperature
Storage temperature
Relative humidity
IP rating
Housing material
Dimensions
Weight
Additional Equipment
Stainless steel adjustable mount
with deck head box
Portable fl ame detector test unit
Deckhead Mounting Box
12–33V DC (polarity insensitive)
550μA
6 to 33V
61mA at 28V
54mA at 24V
20mA at 10V
Remote is a current sink to the negative
line limited to 17mA
Red, Light Emitting Diode (LED)
420Ω in series with a 2V drop
6V (min)
10mA (min)
12V
<1V
1 second
25m for 0.1m² n-heptane fi re, EN54-10, class 1
2m for 0.1m² n-heptane fi re, EN54-10, class 3
class 1 (default) and class 3, as in EN54-10,
clause 5.5
90° cone
UV 185 to 260nm
–40°C to +70°C (no condensation or icing)
–40°C to +85°C
0-95% (no condensation)
66
White polycarbonate V-0 rated to UL94
100mm diameter
40mm height, 48mm in base
150g detector, 210g in base
Part no. 29600-458
Part no. 29600-226
Part no. 45681-217
7