Apollo Smoke Detector XP95 Manuales de instalación

Navegue en línea o descargue pdf Manuales de instalación para Alarma de humo Apollo Smoke Detector XP95. Apollo Smoke Detector XP95 2 páginas. Input/output unit
También para Apollo Smoke Detector XP95: Manual de instalación y mantenimiento (4 páginas), Manual de instalación (2 páginas), Manual de instalación (2 páginas), Manual de inicio rápido (2 páginas), Manual de inicio rápido (5 páginas), Manual de instalación (18 páginas), Manual de instalación (2 páginas)

Apollo Smoke Detector XP95 Manuales de instalación
Protocol bit use:
Output Bit
Function
2
group mode
1 = off
0 = on
1
Alert tone
1 = on
0 = off
0
Evacuation tone
1 = on
0 = off
Fault Finding
Problem
Possible Cause
No response or missing
Incorrect address setting
Incorrect loop wiring (polarity reversed)
Analogue value 1
Sounder test failed
Analogue value 2
VAD failed
Analogue value 3
Sounder and VAD failed
Analogue value 4
Incorrect group address or address setting
Product fails to operate
Control panel has incorrect cause and effect programming
Incorrect group address setting
Tone Table
Part Number
Primary Tone
45681-707
DIN Tone (sweep) *
1200Hz - 500Hz for 1s
For further technical information please refer to PP2478.
© Copyright Apollo Fire Detectors Limited 2013
Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fi re.co.uk Website: www.apollo-fi re.co.uk
39214-789/Issue 1
Input Bit
Function
2
group mode confi rmed
1 = group
0 = individual
1
Alert tone confi rmed
1 = on
0 = off
0
Evacuation tone confi rmed
1 = on
0 = off
Secondary Tone
Continuous*
850Hz
4
XP95 Sounder VAD Base DIN with Isolator

Installation Guide

General
This guide describes the installation of the following sounder
Part number
Product Description
45681-707
XP95 Sounder VAD Base (White) DIN with Isolator
45681-292
White Cap only
45681-293
Red Cap only
Connect the products only to control panels using the XP95 protocol.
The XP95 Sounder VAD Base combines a sounder with a visual alarm and a detector base in one unit.
The VAD is activated whenever the sounder is active and cannot be controlled separately.
The XP95 Sounder VAD Base with short circuit isolator has a yellow LED which illuminates through the mould-
ing if a short circuit is detected on the loop wiring (see Fig 2).
Note: The XP95 Sounder VAD Base is not suitable for outdoor use.
Mounting Instructions
The sounders may be secured to a UK or European standard conduit box or surface mounted (providing
there is access through the surface for cabling). If a detector is fi tted, lock it if required by screwing in the
grub screw on the head with a 1.5mm hex driver (part no 29600-095)
The XP95 Sounder VAD Bases are ceiling mounted devices. For coverage volume information please refer
to PP2478.
Wiring Details
Note: This product is polarity sensitive (supply reversal protected) and will not function if wired incorrectly.
Connect the positive XP95 loop cables to the L2 terminals, the negative loop in to L1 IN and negative loop
out to L1 OUT. (See Fig. 2) Functional earth or screen cables may be terminated to the EARTH connection.
When using the sounder as a stand-alone unit, a cap is available (red cap part no 45681-293 or white cap
part no 45681-292) and is secured with a 1.5mm, AF hexagon socket head screw. A hexagonal driver (part
no 29600-095) is available from Apollo. The isolator LED can be seen through the moulding as shown in Fig 2.
Technical Data
Operating voltage
Sounder output
High tone setting volume
Low tone setting volume*
Sound pressure level information published in document PP2203 and isolator
operation information published in document PP2090, both available on request
Current consumption at 24V DC
quiescent
switch-on surge
sounder VAD operating
VAD frequency
IP rating
*Low tone setting does not comply to EN54–3 and should not be used for fi re
alarm applications
Category
O
n/a
n/a
17—28V DC
nominally 65 to 85dB(A) (Complies with EN54-3)
nominally 50 to 65dB(A)
300μA
1.2mA for 1 sec
14mA
0.5Hz
IP21C
1