Operating Principles
The RW1900-901APO REACH Wireless Manual Call Point is a
wall-mounted device that, when activated, initiates an alarm
on the fire security system. After its use the call point unit can
be simply reset with its proper key, making it immediately
ready for reactivation.
Status LED
When one or more faults are present in the system they are
shown on the LCD and the fault LED is switched on yellow.
LCD is ON only when the tamper switch is not activated
(cover open) regardless of the configuration of the translator
tamper fault. See table 1 for LED status meanings.
Table 1: REACH Wireless Device Status & LED
Indication
Device Status
Power Up
Power Up (dip-switch ON)
Blinks alternatively green/red four
Entering Wake-Up
Link Success
Enters wake-up mode and signals
Link Failure
'Entering wake-up mode' following
Normal Condition
Activation
Battery Faults
Tamper Fault
Replaced
Device Addressing
Device addressing is handled by the REACH Wireless Loop-
Interface device (RW1700-030APO.
Devices are soft-addressed automatically when pairing with
the Loop Interface and can be changed manually. Hard-
addressing using Apollo XPERT cards are not supported.
Communication
REACH Wireless Devices use 'radio-frequency' wireless
communication to connect to the Loop-Interface.
The Loop-Interface (RW1700-030APO) translates the wireless
communication into wired Apollo protocol communication,
with each device addressable individually by the fire panel.
See datasheets for the Loop-Interface for more information.
Tamper detection
REACH Wireless devices contain an anti-tamper mechanism.
In the event of removal from its base, it sends a tamper
detection message to the Loop-Interface.
Tampering detection is not signalled visually by the device
LED.
LED Indication
Blinks green four times
Blinks red four times
times
Blinks green four times, then
repeats
this failure
LED off
Red on 1s, period 2s
LED off
LED off
Blinks amber two times
EMC Directive 2014/30/EU
REACH Wireless Manual Call Point complies with the
essential requirements of the EMC Directive 2014/30/EU,
provided that it is used as described in this datasheet.
A copy of the Declaration of Conformity is available from
Apollo on request.
Construction Products Regulation (EU) 305/2011
The REACH Wireless Manual Call Point complies with
the essential requirements of the Construction Products
Regulation (EU) 305/2011
A copy of the Declaration of Performance is available from
Apollo on request.
PP5115/2022/Issue 1