Apollo ApolloPress APL77V10711 Manual de instalación, uso y mantenimiento - Página 2

Navegue en línea o descargue pdf Manual de instalación, uso y mantenimiento para Unidad de control Apollo ApolloPress APL77V10711. Apollo ApolloPress APL77V10711 3 páginas. Ball valve

3. Test the system for leaks in accordance with normal practice and local codes.
Troubleshooting
SYMPTOM
Wrong jaw set or press ring for the
tube size or material.
The jaw set or ring was not square
to the tube.
Press cycles
produced are
Jaw contour was not aligned with
not complete.
the valve contour.
The jaw set or ring has exceeded life
expectations and may have failed.
Excessively large
Copper material build-up on jaws or
or sharp fins
rings in the contoured profile area
present at press
near jaw or ring tips.
joint parting line
where jaw or
ring tips come
Excessively worn or damaged jaw
together.
sets or rings.
Jaws stick to
Copper material build-up on jaws or
valve excessively
rings in the contoured profile area
after completing
near jaw or ring tips.
joint.
OPERATION
The valve handle is marked showing proper rotation direction for "ON" and "OFF" positions. Standard rotation is clockwise for
"OFF" (closed) and counterclockwise for "ON" (open).
MAINTENANCE
Normal stem packing wear can be compensated for by tightening the packing gland nut. The top nut and the lever
may need to be removed for easy access to the packing nut. Tighten the packing nut clockwise in 1/8 turn increments until
observed leakage stops. (Packing wrench part number H371400 is available to ease this operation.) Reinstall the handle
and handle nut after adjustment.
ADDITIONAL RESOURCES
ApolloPress
®
Installation and Pressing Instructions
http://cdn.conbraco.com/apollopress/documents/APOLLOPRESS_Installation_Instructions.pdf
ApolloPress
®
Approved Applications
http://cdn.conbraco.com/apollopress/documents/APOLLOPRESS_Approved_Applications_Sheet.pdf
ApolloPress Jaw Compatibility
http://cdn.conbraco.com/apollopress/documents/APOLLOPRESS_Jaw_Compatability.pdf
ApolloPress FAQ's
http://cdn.conbraco.com/apollopress/documents/APOLLOPRESS_FAQs.pdf
Aalberts integrated piping systems Americas, Inc. Pageland S.C. 29728 Telephone (704) 847-9191 Apollovalves.com
POSSIBLE REASONS
SOLUTION
Install correct jaw set.
Redo the joint with new tube and
valve and make sure that the jaw set
or ring is square to the valve.
Redo the joint with new tube and
valve and make sure that the jaw set
or ring is square to the valve.
If cracked, replace old jaw set with a
new jaw set and redo the joint using
a new tube and valve.
Clean jaw sets or rings in the
contoured area using metal
polishing pads such as Scotch-Brite®.
Refer to the press tool's
maintenance section for proper
instructions
Discard jaws or press ring and
replace with a new jaw set.
Clean jaw sets or rings in the
contoured area using metal
polishing pads such as Scotch-Brite®.
Refer to the press tool's
maintenance section for proper
instructions