Duro Dyne DuroZone RED-4 Manual de instrucciones de instalación - Página 8

Navegue en línea o descargue pdf Manual de instrucciones de instalación para Sistemas de control Duro Dyne DuroZone RED-4. Duro Dyne DuroZone RED-4 16 páginas. Zone control system

Automatic Contractor Test (Version 1.70)
the Automatic Contractor test (ACt) can
be started at any time by pressing and holding
the timer Reset switch for 10 seconds.
the test can be terminated at any time by
pressing the timer Reset switch again.
When the test is started all calls are terminated and
all dampers will be closed. the Status LED will be on
continuously during the test.
Step1. Zone1 Thermostat Test
the DPR1 LED will turn On and
the Cool, Heat, Fan, or EM Heat
LED will turn On indicating the
state of the Zone1 thermostat. If
the Cool, Heat, Fan and EM Heat
LEDs are all Off, there is no call at
the thermostat. Step 1 will run 30
seconds.
Step2. Zone2 Thermostat Test
now the DPR2 LED will turn On
and the Cool, Heat, Fan, or EM
Heat LED will turn On indicating
the state of the Zone2 thermostat.
Step 2 will run 30 seconds.
Step3. Zone3 Thermostat Test
now the DPR3 LED will turn On
and the Cool, Heat, Fan, or EM
Heat LED will turn On indicating
the state of the Zone3 thermostat.
Step 3 will run 30 seconds.
Step4. Zone4 Thermostat Test
now the DPR4 LED will turn On
and the Cool, Heat, Fan, or EM
Heat LED will turn On indicating
the state of the Zone4 thermostat.
Step 4 will run 30 seconds.
Step5. Damper Test
now all of the dampers will be
opened and the indoor fan is
activated. Step 5 will run for 1
minute. You can terminate the
test at this time by pressing the
timer Reset switch. You might want to change
the thermostats and again run the test.
Step6. Damper4 Test
now Damper4 will close and the indoor fan
remains activated. If Damper4 is used as a zone
damper you should not feel airflow at Zone4
and the other zones should be open. the DPR4
LED will be OFF. If Damper4 is used as a fresh
air damper it also should be closed. Step 6 will
take 1 minute.
DuroZone
RED4 - InStALLAtIOn InStRUCtIOnS PAGE 8
RED4 InstrManual-7-1-10.indd 8
Step7. Damper3 Test
now the Damper3 will close and the indoor fan remains
activated. You should not feel airflow at Zone3 and the
other zones should be open. the DPR3 LED will be OFF.
Step 7 will run 1 minute.
Step8. Damper2 Test
now Damper2 will close and the indoor fan remains
activated. You should not feel airflow at Zone2 and the
other zones should be open. the DPR2 LED will be OFF.
Step 8 will take 1 minute.
Step9. Damper1 Test
now Damper1 will close and the indoor fan remains
activated. You should not feel airflow at Zone1 and the
other zones should be open. the DPR1 LED will be OFF.
Step 9 will take 1 minute.
Step10. Stage1 Heating Test
All dampers will be open now and the stage1 heating is
activated. Check that heated air is entering the zones.
the Heat LED will be On continuously. Step 10 will run
1 minute.
Step11. Stage2 Heating Test
now the stage2 heating is also activated. Check that
heated air is entering the zones. the Heat LED will be
blinking. Step 11 will run 1 minute if it is on a Heat
Pump System. Add 1 minute if not on a Heat Pump for
the purge cycle.
Step12. Stage3 Heating Test
If a heat pump is selected, the third stage heating will be
activated for 1 minute. then the heating will be turned
Off and the indoor fan run for 1 minute to purge the
heat. Step 12 will run 2 minutes.
Step13. Stage1 Cooling Test
the Stage1 cooling is now turned On and Cool LED will
be On. Check that cool air is entering the zones. Step 13
will run 1 minute.
Step14. Stage2 Cooling Test
now the Stage2 cooling is also turned On and Cool LED
will blink. Check that cool air is entering the zones. Step
14 will run 1 minute.
After the stage2 cooling has run for 1 minutes the cooling
will be turned Off. the indoor fan will run for 1 minute
to purge the cooling and then the panel will return to
normal operation.
For the most updated product information,
please visit our website
www.durodyne.com
©2010 Duro Dyne Corporation
Printed in USA 6/2010
BP035428
7/9/2010 5:34:53 PM