Datakom DKG-117 Manual del usuario - Página 4
Navegue en línea o descargue pdf Manual del usuario para Relés Datakom DKG-117. Datakom DKG-117 12 páginas. Synchroscope and check synch relay
También para Datakom DKG-117: Manual del usuario (12 páginas)
DKG-117 User Manual
1.3 Wiring the Unit
WARNING: THE UNIT IS NOT FUSED.
Use external fuses for Busbar phase: R, Generator
phase: U, Battery positive: BAT(+).
Install the fuses as nearly as possible to the unit in a
place easily accessible for the user.
The fuse rating should be 6 Amps.
WARNING: ELECTRICITY CAN KILL
ALWAYS disconnect the power BEFORE
connecting the unit.The fuse rating should be 6 Amps.
1) ALWAYS remove the plug connectors when inserting wires
with a screwdriver.
2) ALWAYS refer to the National Wiring Regulations when
conducting installation.
3) An appropriate and readily accessible set of disconnection
devices (e.g. automatic fuses) MUST be provided as part of the
installation.
4) The disconnection device must NOT be fitted in a flexible cord.
5) The building mains supply MUST incorporate appropriate
short-circuit backup protection (e.g. a fuse or circuit breaker)
of High Breaking Capacity (HBC, at least 1500A).
Use cables of adequate current carrying capacity (at least 0.75mm
and temperature range.
V-01
(24.03.2014)
2
)
- 4 -