Elsner Suntracer KNX-GPS Especificaciones técnicas e instrucciones de instalación - Página 3

Navegue en línea o descargue pdf Especificaciones técnicas e instrucciones de instalación para Estación meteorológica Elsner Suntracer KNX-GPS. Elsner Suntracer KNX-GPS 12 páginas.

1.1. Technical specifications

Housing
Colour
Mounting
Protection category
Dimensions
Weight
Ambient temperature
Operating voltage
Auxiliary current
Bus current
Data output
BCU type
PEI type
Group addresses
Allocations
Communication objects
Heating rain sensor
Measurement range
temperature:
Resolution (temperature)
Accuracy (temperature)
Measurement range wind
Resolution (wind)
Accuracy (wind)
Measurement range
brightness
Resolution (brightness)
Accuracy (brightness)
The product conforms with the provisions of EC guidelines
EMC Directive 2004/108/EC
Weather Station Suntracer KNX-GPS light • Version: 15.07.2013 • Technical changes reserved. Errors reserved.
3
Plastic material
White / translucent
On-wall
IP 44
approx. 96 × 77 × 118 (W × H × D, mm)
approx. 170 g
Operation -30...+50°C, Storage -30...+70°C
12...40 V DC (12...28 V AC)
max. 185 mA at 12 V DC
max. 81 mA at 24 V DC
Residual ripple 10%
max. 8 mA
KNX +/- bus terminal plug
Own micro controller
0
max. 254
max. 255
222
approx. 1.2 W (230 V and 24 V)
-40...+80°C
0.1°C
±1°C
at -10...+85°C
±1.5°C at -25...+150°C
0...35 m/s
0,1 m/s
at ambient temperature -20...+50°C:
±22% of the measurement value when incident flow is
from 45...315°
±15% of the measurement value when incident flow is
from 90...270°
(Frontal incident flow corresponds to 180°)
0...150 000 lux
1 lux
at 0...120 lux
2 lux
at 121...1 046 lux
63 lux at 1 047...52 363 lux
423 lux at 52 364...150 000 lux
±35%
Description