Product description

The Power Supply Systems KNX PS640+ and KNX PS640+USB deliver a 29 V bus
voltage for the KNX system and 24 V DC supply voltage for 24 V devices. Special
operating conditions such as short circuit, electrical surge, overcharge or excess
temperature are recorded and may be read off on the display. The present power
discharge is displayed as well. It is possible to reset the connected bus devices directly
by means of the key pad.
In addition all functions can be realised via the bus, too, e. g. the transfer of malfunction
messages and operating data and a time/period reset. Malfunction messages are stored
by the KNX PS640+(USB).
Functions:
Delivers a 29 V KNX bus voltage (reduced), output current max. 640 mA, short-
circuit proof
Delivers 24 V DC (not reduced), output current max. 150 mA
Reset of a line directly on the device
Record of operating hours, overload, external overvoltage, internal overvoltage,
short circuit and excess temperature
Display of operating data bus voltage, bus current and temperature of the device
The display may be shown in German, English, Spanish or Dutch
Bus connection for data transfer (e. g. malfunction messages, operating data)
Possibility for reset and diagnostics via the bus
Only KNX PS640+USB: USB interface for bus access via PC
The programme file for KNX software ETS (format VD2) is ready for download on the
Elsner Elektronik website at www.elsner-elektronik.de in the "Service" menu.

Technical data

Housing
Colour
Mounting
Protection category
Dimensions
Weight
Ambient temperature
Ambient air humidity
Operating voltage
Power consumption Standby
Outputs
Data output
Plastic material
White
Snap-on fitting on mounting rails
IP 20
approx. 123 x 89 x 61 (W x H x D, mm), 7 width units
approx. 370 g
Operation -5...+45 °C, storage -25...+70°C
max. 95% RH, avoid bedewing
230 V AC , 50 Hz
approx. 2.3 W
KNX bus voltage 29 V (reduced),
Output current max. 640 mA, short-circuit proof
24 V DC (not reduced), Output current max. 150 mA
KNX data
KNX +/- bus terminal plug
3