Basically the display can show a two-row or three-row text (e. g. for measured va-
lues) or a temperature controller. You can switch between the two types by pres-
sing one of the buttons, if this has not been disabled in the ETS.
5.1. Mode display and manual temperature controller
Depending on the ETS setting selected, the mode display will only display show
the current target value, or the base target value setting with scale display. The ma-
nually adjustable range can be set in the ETS.
The following display options are available:
Fig. 4
Mode display with current target value and/or
base target value
Fig. 5
Mode display with scale display for adjusting
the base target value.
The control position in the image reads "Base
target value reduced".
Fig. 6
Mode display with scale display and number.
Shows the set target value change.
The control position in the image reads "Base
target value reduced to 1.0°".
Fig. 7
Mode display with scale display and range.
Shows the possible adjustment range (as set in
the ETS).
The control position in the image reads "Base
target value reduced".
Fig. 8
Mode display with scale display, range and
number.
Displays the possible adjustment range (as set
in the ETS) and the set target value change.
The control position in the image reads "Base
target value reduced to 1.0°".
Symbols
Comfort mode.
Standby mode.
Comfort (present) target
Standby (absent during day)
temperature will be used.
target temperature will be
used.
Eco mode.
Building protection mode.
Night target temperature
Building protection target
will be used.
temperature will be used.
The symbol will blink when
the mode has been activa-
ted but the activation delay
has not yet expired.
Heating mode.
Cooling mode
Heating will be provided.
Cooling will be provided.
Priority (points)
Fig. 9
In "HVAC mode with 2x 8 bits" control mode,
points are shown under the symbol, to indicate
the running priority of the current mode.
One point: Priority 1/priority control. It is not possible to adjust the temperature au-
tomation system manually. Neither the target temperature nor the operating mo-
des can be changed using the buttons on the unit.
Two points: Priority 2. The target temperature and operating mode can be changed
using the buttons.
5.2. Change ambient temperature with the buttons
If the mode display is active, the target ambient temperature and the operating
mode can be changed manually using the buttons. The button functions can be
blocked in the ETS or be suppressed for Priority 1 operating modes. The individual
operating modes can also be locked for manual selection in the ETS.
Decrease tar-
briefly press
Ambient temperature in the
get tempera-
left button
current mode is decreased.
ture (-)
The sep-size is defined in the
ETS (0.1°C to 5°C).
Increase tar-
briefly press
Ambient temperature in the
get tempera-
right button
current mode is increased.
ture (+)
The sep-size is defined in the
ETS (0.1°C to 5°C).
Sensor KNX VOC/TH-UP Touch CH
Change mode
press
left or right button
longer than 2 secs.
Extend Com-
in Eco mode:
fort mode
press both buttons
at the same time
longer than 2 secs.
6.
Disposal
After use, the device must be disposed of in accordance with the legal regulations.
Do not dispose of it with the household waste!
Sensor KNX VOC/TH-UP Touch CH • Version: 30.11.2021 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Changes between the opera-
ting modes Comfort, Standby,
Eco and Building Protection (if
deblocked in the ETS).
Switches from Eco to Comfort
mode again for a certain time
(e. g. if the rooms are used lon-
ger in the evening).
The period is defined in the
ETS (up to 10 hours). The time
remaining in Comfort mode is
displayed.
2