Dust Free BIO-FIGHTER Ultra-Flex 1S14 Manual de instalación y funcionamiento - Página 5

Navegue en línea o descargue pdf Manual de instalación y funcionamiento para Equipos de iluminación Dust Free BIO-FIGHTER Ultra-Flex 1S14. Dust Free BIO-FIGHTER Ultra-Flex 1S14 7 páginas. Ultraviolet light systems

BIO-FIGHTER® ULTRA-FLEX INSTALLATION & OPERATION MANUAL
INSTALLING THE AHU VIEWPORT(s)
The Ultra-Flex comes with UV-C safe viewports
that must be installed separately. To install the
viewport, select a location near the lamp
installation and drill a 1/2" hole in the duct.
Then press the viewport into the hole.
CONNECT POWER AND CHECK OPERATION
Connect the device to 120V-240V power.
(Fig.8)
The device power switch must be turned on
and device checked for operation using the
viewport(s). The lamp(s) should be radiating a
bright blue light.
Power Cord
Connect black and
white wires to
120V-240V power.
Fig. 8 Power cord connection.

OPERATION

Under normal conditions the Bio-Fighter®
Ultra-Flex should be operated continuously to
extend the life of the lamp(s), and to increase
the effectiveness in disinfecting the location
selected. A convenient power switch is located
on the device, and should be turned off before
any maintenance on the device or HVAC sys-
tem is performed.
WARNING
UV-C Light Hazard.
UV-C light can cause temporary or permanent loss of
vision, and sunburn. Take precautions to protect eyes
and skin from direct exposure.

TROUBLESHOOTING

Maintenance and troubleshooting should be
performed by a qualified technician.
Device fails to operate.
1. Check that device is connected to proper
2. Check that fuse is in good working order.
3. Check that ballast is receiving correct
4. Check continuity of lamp filaments.
5. Check that wires are properly connected to
6. Check that lamp is properly connected to
Connect green wire

FUSE REPLACEMENT

to ground.
1. Turn off power to the equipment.
2. Unscrew the knob marked "Fuse" and
3. Install new fuse and screw knob back in
4. Turn on power to the equipment.
5
power.
Replace the fuse if necessary.
power. Replace ballast if necessary.
(Replace lamp if necessary.)
lamp and ballast.
lamp receptacle.
remove fuse.
place. Only use a 250V/3 amp fuse.