CBC EA 900RT 1KVAR Manual del usuario - Página 14

Navegue en línea o descargue pdf Manual del usuario para UPS CBC EA 900RT 1KVAR. CBC EA 900RT 1KVAR 18 páginas.

TRUE ON LINE UPS

8. Technical data

8.1 Electrical specifications
INPUT
Model No.
1K
2K
Voltage
115~300VAC
Frequency
7A
12A
Current(A)
OUTPUT
Model No.
1K
2K
Power rating
1kVA/0.7kW 2kVA/1.4kW 3kVA/2.1kW 6kVA/4.2kW 10KVA/7kW
Voltage
220/230/240 (1 2%)VAC
Frequency
50/60 (1 0.2%)Hz (Battery mode)
Wave form
BATTERIES
Model No.
1KS
2KS
3 12V
8 12V
Voltage
7.0Ah
7.0Ah
8.2 Operating Environment
Ambient Temperature
Operating humidity
Altitude
Storage temperature
24
3K
6K
10K
176~276VAC
(46~54)Hz /(56~64)Hz
16A
30A
47A
3K
6K
10K
220/230/240 (1 1%)VAC
50/60 0.05Hz
Sinusoidal
3KS
6KS
10KS
8 12V
20 12V
20 12V
7.0Ah
7.0Ah
9.0Ah
0
to 40
< 95%
< 1000m
0 ~40
8.3 Typical stored energy time (Typical values at 25
minutes:)
Model No.
100 % Load
1K
2K
3K
6K
10K
8.4 Dimensions and weights
Dimensions W D H (mm)
Model No.
1KS
145 400 220
1KH
145 400 220
2KS
192 460 340
2KH
192 460 340
3KS
192 460 340
3KH
192 460 340
6KS
260 570 717
6KH
260 570 717
10KS
260 570 717
10KH
260 570 717
Only the units with CE markings are comply with the following standards:
1) For 1K / 2K / 3K
EN62040-1-1 (safety)
Conducted Emission:EN50091-2..............................................Class B
Radiated Emission: EN50091-2................................................Class B
TRUE ON LINE UPS
in
50 % Load
5
14
9
21
5
15
8
23
5
12
Net Weight(kg)
14
7
34.5
15
35.5
16
90
35
93
38
25