DV Power TRT30C Manual - Página 10
Navegue en línea o descargue pdf Manual para Transformador DV Power TRT30C. DV Power TRT30C 19 páginas. Three-phase transformer, turns-ratio test instrument
TRT30C
3.2 Setting the Measurement Parameters
Five seconds after the first (initial) message on the display, the TRT30C automatically changes the display
to the CONFIGURATION menu and the green LED lights up. By pressing
the CONFIGURATION menu and the MEMORY menu.
Press
in the HV CONFIG field to select the test mode to be performed. A list of the available test
UP/DOWN
modes is shown in tables 2 and 4.
HV
LV
Config.
Config.
D
displayed
Y
displayed
YN
displayed
Z
displayed
ZN
displayed
AVGD
hidden
SINGLE
hidden
CT
hidden
TRUE 3~
hidden
TEST
AUTO
hidden
Press
to choose one of the available options in the configuration menu.
ENTER
1. If the vector group is selected, the TRT30C will perform both the true three-phase test by applying true
three-phase test voltage and the phase by phase test by applying single phase test voltages to all phases
in turn.
2. If SINGLE is chosen, the TRT30C will test a single phase transformer by applying the single phase test
voltage between 1U/H1/A and 1N/H0/N.
3. If CT is chosen, the TRT30C will test a current transformer by applying the single phase test voltage
between 1U/H1/A and 1N/H0/N.
4. If AUTO is chosen, the TRT30C will display the special menu for autotransformers to the user.
5. If the AVGD option is selected, the TRT30C will automatically detect the vector group of the transformer
under test.
6. If TRUE 3~ TEST is selected, the TRT30C will perform the true three-phase test by applying the true
three-phase test voltage.
Table 3 lists the available vector groups in this menu.
Configuration
D-D, D-Z, D-Zn, Z-D, Zn-D, Y-Y, Y-Yn, Yn-Y, Yn-Yn
D-Y, D-Yn, Y-D, Y-Z, Y-Zn, Yn-D, Yn-Zn, Z-Y, Z-Yn, Zn-Y, Zn-Yn
M-T030CN-203-EN
Table 2: Available options in the configuration menu
Ph
Comment
Displacement
displayed
Delta winding
displayed
Star winding
displayed
Star winding with neutral point
displayed
Zigzag
displayed
Zigzag with neutral point
hidden
Automatic vector group
detection
hidden
Single-phase transformer
hidden
Current transformer (CT)
hidden
Only true three-phase test
hidden
Autotransformer menu
Table 3: Available vector group configurations
10
Getting Started
the user can switch between
SET
Test mode
Phase by phase test
using single-phase
voltage in turns
&
the true 3-phase test
using 3-phase voltage
Single phase test
using single-phase
voltage
True 3-phase test
using 3-phase voltage
See table 4
Displacements
0-2-4-6-8-10
1-3-5-7-9-11