Replace UV-C Tube
Warning
Please cut off the power before replacing the UV-C tube.
Tools: Electric batch, Screwdriver, etc.
Duct
1
M4 Srew
PCO-kit
Duct
2
protective
net
+
Screw
PCO-kit
Base
1. Confirm that the power is disconnected.Remove the 4 screws fixing the PCO-kit
(keep the screws).
2. Remove the PCO-kit. Use a screwdriver to remove the screws that fix the
protective net, and rotate the protective net in the direction of the arrow in the
figure 2, then slowly take out the protective net.
3. Pull out the UV-C tube slightly hard (do not damage the UVC-tube). Insert the
new UV-C tube into the lamp holder.
4. Insert the protective net and rotate the protective net in the direction shown in
Figure 4. When the screw holes on the protective device are aligned with the
screw holes on the base, use a screwdriver to lock the screws. Finally, fix the
PCO kit back to the air duct.
5. Re-power on, turn on the power switch of PCO-kit, and use a small screwdriver
to hold down the reset button to make the digital tube display the value "8000".
3
4
protective
net
Screw
PCO-kit
5
6
Environmental Protection And Safety
Scrap Disposal: Treat separately with domestic waste and recy as much as possible.
The UV-C tube is broken treatment methods:
1. Open the window to ventilate as soon as possible.
2. Quickly clean up the debris and drop solid mercury, put the garbage bag
containing solid mercury in the outdoor waste lamp and battery treatment box.
3. Evacuate the personnel and do not get into the room within 15 minutes.
Fault Rectification
If the PCO-kit cannot operate after being powered on, please check the following
items. During the repair process, the disassembly and assembly steps are
involved, please refer to the UV-C tube replacement steps.
Fault Code
Base
Check steps
Check whether the wind speed sensor has a short circuit or an
open circuit.
1. Is the UV-C tube plugged in?
Pull out the UV-C tube again and insert it again.
2. The photosensitive components on the control circuit are
damaged. Replace the control board.
1. Check whether the PCO-kit is in good contact with the air
duct? No outside light affects PCO products.
2. Remove the protective net, pack the photosensitive
components with black insulating tape, power on to confirm
whether the alarm is cleared, if not cleared, replace the
control circuit board.
1. Confirm whether the electronic ballast connection line is
normal?
2. Replace with a new ballast of the same model
Replace the UV-C, and long press the Reset button to restore
the value of the digital tube to 8000.