4PRO 125A-4P-di Manual de inicio rápido - Página 3

Navegue en línea o descargue pdf Manual de inicio rápido para Interruptor 4PRO 125A-4P-di. 4PRO 125A-4P-di 7 páginas. Automatic transfer switch

4PRO 125A-4P-di Manual de inicio rápido
External display controller

Settings menu

ON
N
R
OFF
Key-press instruction
When controller is working, press Set button on the LCD display front panel. Under the setting menu, press "
button to scrol the setting items. Press "
setting menu.
N
S
OFF
Password input, press
to change position,
press
to input the password :888
Normal Power Under voltage transfer value set, Press
increase press
decrease
Normal Power over voltage transfer value set, Press
increase, press
decrease
Transfer delay time setting, Press
increase,
press
decrease
Reserve Power Under voltage transfer value setting, Press
increase, press
decrease
Reserve Power Over voltage transfer value setting, Press
increase, press
decrease
Recovery time delay, Press
increase,
press
decrease
Generator Start time delay, Press
increase, press
decrease
Generator stop delay time setting, Press
increase, press
decrease
Transfer Mode setting, press
to change
the transfer mode (the last digit: 0 - no source priority;
1 - source # I priority, 2 - source # II priority).
" or
"
Factory default value settings
Normal power under voltage transfer value: 187V
Normal power Over voltage transfer value: 2 3V
Reserve power under voltage transfer value: 187V
R
Reserve power Over voltage transfer value: 2 3V
Transfer delay time: 5 sec
Recovery delay time: 5 sec
Generator start delay time : 5 sec
Generator stop delay time: 5 sec
Transfer Mode: Power Grid - Power Grid
16
17
18
19
20
21
22
" button to modify item value settings. Press "
5
5
Generator exerciser timer date setting, press
change the timing of date (from 001 to 031).
Generator exerciser timer week setting, press
change the timing of week (000 - Sunday;001-Monday;
002 - Tuesday; ....; 006 - Saturday).
Generator exerciser timer hour setting, press
change the timing of hour (from 000 to 023);
Generator exerciser timer minute setting, press
change the timing of minute (from 000 to 059).
Generator exerciser timer second setting, press
change the timing of second (from 000 to 059).
Generator exerciser time duration hour setting, press
change the timing of hours (from 000 to max. 500 hours).
Generator exerciser time duration minute setting, press
to change the timing of minute. ( From 000 to 059 min.)
"
or
"
" button to exit the
-
to
to
to
to
to
to
"
3
-