HI tecnologia P7C Manual de conexión - Página 6

Navegue en línea o descargue pdf Manual de conexión para Controlador HI tecnologia P7C. HI tecnologia P7C 8 páginas.

HI tecnologia P7C Manual de conexión
User Manual - P7C Controller
IMPORTANT: The main Rack MRK AC power supply can be from 85 to 265 VAC or 100 to 400
VDC. The main Rack MRK DC power supply can be from 10 to 36VDC. We recommend the use
of a rigid or flexible 2,5mm2 wire (7mm stripped) or flexible 1,5mm2 wire with eyelets terminal.
Earth-Protection Connector
Note: The modules can have lever connectors (for the new modules) or screw connectors.
IMPORTANT: Use connector
This connection with the rack can be made at the bottom side, on the top side or both ways.
Addressing
Racks addresing
The expansion racks are coupled on the main rack right side, being possible to couple up to five
expansions. Each rack has a three straps
(between the connectors
of the rack, using jumpers
Identification
Main Rack
Expansion Rack 01
Expansion Rack 02
Expansion Rack 03
Expansion Rack 04
Expansion Rack 05
1 - Check the Notes and Acronysms List at the beggining of this document
Ref.: PMU107001
1
of the third and fourth slots
1
, as the following:
1
Version: 1.0.07
OR
Faston 6.3 totally isolated for 1mm2 green and yellow cable.
set named J1, J2, J3. This set, placed at the backplanes
1
) must be configured according to the position
1
J1
J2
J3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
Release: 10/20/10
Caption:
ON: with jumper
1
OFF: without jumper
1
Caption:
Technical Specifications
,
1
35