Great Lakes Air Products GPS-500 Manual de instrucciones - Página 8

Navegue en línea o descargue pdf Manual de instrucciones para Deshumidificador Great Lakes Air Products GPS-500. Great Lakes Air Products GPS-500 14 páginas. Compressed air dryer

SEQUENCE CONTROLLER

Time cycles are part of the equipment design that have been accurately set in the factory and should
not be field adjusted. Timing changes are possible for custom applications but always consult the
factory prior to changes. The following are the standard time cycles for your equipment.
Drying Each Tower
Purging Each Tower
Drain Time Sequence
The standard heatless regenerative air dryer is controlled by a CMOS logic system designed
specifically for compressed air dryers. The controller is preset in its function with adjustments available
by moving jumper pins.
EXT/INT Configuration
50/60 CYCLE Power Input
HEAT/HTLS Type
STD/TEST
The test cycles are for startup and troubleshooting do not operate in test for normal operation!
Type
Time
Standard
Main
240 Min.
Purge
235 Min.
Heat
150 Min.
Notes: 1. Open signifies that the jumper is completely removed and connects no pins.
2. Time sequence vs jumper status (assumes power frequency correlation)
If an optional PLC control is operating the dryer sequence, a program and manufacturer's warranty will
be included with this manual. Consult factory prior to any changes to PLC programs.
5 Minutes or indefinite period with the Demand Cycle Controller
option.
4 Minutes / 30 Seconds
Field Adjustable
Selects external or internal configuration for heating when HEAT is
selected on the HEAT/HTLS jumper pin.
Selects feed power frequency of 50 or 60 Hz.
Selects a basic design configuration of Heated or Heatless.
Selects a standard operational timing sequence or a test sequence
Heated (HEAT)
Test
Open
48 Min.
30 Sec.
47 Min.
20 Sec.
30 Min.
10 Sec.
GPS Heatless Regenerative
Page 8 of 14
Heatless (HTLS)
Standard
Test
300 Sec.
150 Sec.
260 Sec.
130 Sec.
(none)
(none)
Time Cycle Display
00 03
Hours : Minutes
The Time Cycle Display shows
the current online towers time
of operation (Adsorption)
Led Status Indicator
If the green led status indicator
is blinking it indicates the
controller is in an active
regeneration cycle. If the
indicator is solid, it indicates
that the controller is in a
demand standby mode waiting
for a signal from an external
source to complete a circuit
between terminal #11 & #12
Open
20 Sec.
10 Sec.
(none)