ExHAUST CHIMNEy & FAN TRAy - ES SERIES
InStallatIon of adJUStable eXhaUSt ChImney
Before installation, remove the rear, top knockout from the enclosure.
Place assembled chimney on top and attach from the inside using
#10-32 screws. Raise the outer section so the seal touches the ceiling.
InStallatIon of fan tray
Place fan tray onto fixed portion of the chimney, ensuring cord is
hanging through the chimney and into the enclosure. The fan will rest
on four studs. Secure the fan with #10-32 nuts from the inside of the
enclosure. Available Chimney and Fan Trays include:
GL-EC-42-1832
GL-EC-42-3246
GL-ECFT42
Please note: In order for the exhaust
chimney and fan tray to be effective,
a solid rear door must be used.
Please call your distributor/
Great Lakes representative
for more information.
Cord for Fan Tray to
Exit back Through
the Chimney and
Rear of Enclosure
#10-32 x 1/2"L
Mounting Screws
(Qty. 4)
Mounting Holes
For #10-32
Screws (Qty. 4)
12
Chimney for 42"D enclosure with an adjustable
range of 18" to 32"
Chimney for 42"D enclosure with an adjustable
range of 32" to 46"
Fan Tray for 42"D enclosure, 1200 CFM
Adjust Chimney to
Desired Height; Use
Screwdriver to Punch
Out Appropriate
Knockout for Knob
(Qty. 2 - Both Sides)
Drop Fan Tray Into
Fixed Bottom Portion
of Chimney - Notches
Should Fall Onto Studs
in Chimney
Install Nuts Onto
Studs from Bottom
Inside Enclosure
(Qty. 4)
Use Screwdriver
to Punch Out
Rear Knockout