SPECIFICATIONS
Humidity (typical +/- 2% RH), Temperature (typical +/- 0.2C). Calibrated
using Automatic Self Calibration (ASC) or it can be forced to calibrate
itself using an algorithm. This is called FRC or Forced Recalibration.
Dedicated CO2 sensor with a range of 0 - 40'000 ppm, accuracy of +/-
30ppm (0-5000ppm, 25C). Drift +/- 50ppm over 400-5000ppm range
over lifetime of 15 years
VOC sensor with derived e-CO2: Typical Accuracy - 15% of measured
value. TVOC: 0 – 60'000 ppb. CO2eq: 0 – 60'000 ppm. Drift 1.3% of the
measured value per year.
Occupancy Sensor based on Passive Infra-Red (PIR) with detection range
of 4m with 15-degree angle.
Light Sensor. Ambient light sensor, <100 mlx resolution, High accuracy
UV index sensor, Matches erythermal curve
Sound sensor with 40-120dB response for 100 Hz to 10Khz.
PM2.5, PM10 sensor (optional). Detection range of 0-1000ug/m3
and accuracy of +/-10ug/m3 (PM2.5, 0-100ug/m3) or +/-25ug/m3
(PM10, 0-100ug/m3). Maximum long-term mass concentration
precision limit drift
• 0 to 100 μg/m3 ±1.25 μg/m3 / year
• 100 to 1000 μg/m3 ±1.25 % m.v. / year
RF capabilities, 902-928Mhz proprietary RF for communicating
sensor values with gateway.
Bluetooth: BLE 4.2 for commissioning, triangulation and
communication to wireless sensors.
Relays rated at 110V ac, 24V dc/1A
Analog Outputs 0-10V/4-20ma (max load of 20mA per channel)
2.8" 240x320 pixel TFT display.
Touch slider for temperature control along with 3 mechanical
buttons.
4 wire RS485 interface in Regular variant with an optional 5V power
line.
3 wire sensor bus for daisy chained sensor communication and
3V power
24V ac/dc (+/-15%) powering
Power from a Daikin IDU using P1P2 lines
Power Consumption
Operating range: Humidity 20-85% non-condensing. Temperature
0 to 122°F (-17 to 50°C)
Specifications
support75F.io|
HS3600/DKN509
Y
Y
Y
Y
Y
Y
Y
Y
Y
6 Relays
3 outputs
Y
Y
Y
Y
Y
-
1W nominal (2.5W
max)
Y
+1 888 612 7575 (USA) or 1800 121 4575 (INDIA)
DKN510
DKN510
P1P2 Base
P1P2 Plus
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
No Relays
2 Relays
No outputs
2 Outputs
Y
Y
Y
Y
-
-
Y
Y
Y
Y
Y
Y
1.3W max
1.3W max
Y
Y