ADEMCO ADEMCO VISTA-15PSIA Manual de programación - Página 10
Navegue en línea o descargue pdf Manual de programación para Sistema de seguridad ADEMCO ADEMCO VISTA-15PSIA. ADEMCO ADEMCO VISTA-15PSIA 17 páginas. Ademco vista series security system
También para ADEMCO ADEMCO VISTA-15PSIA: Manual de instalación rápida (2 páginas), Manual del usuario (20 páginas), Manual de instalación rápida (2 páginas), Manual de instalación rápida (2 páginas), Manual rápido (2 páginas)
∗ ∗ ∗ ∗ 79 Menu Mode
(press ∗ ∗ ∗ ∗ 79 while in Programming mode)
The *79 Device Mapping Worksheet is on page 14.
ENTER OUTPUT NO.
01-18 = VISTA-20P relays/X-10; 01-08, 17, 18 = VISTA-15P relays/X-10
[∗] to continue
OUT NORM LOW (appears only for triggers 17/18)
0 = no (standard default); sets the output level normally high
1 = yes; sets the output normally low (can be used for resetting 4-wire
smoke detectors)
[∗] to return to Output Number prompt
OUTPUT TYPE
0 = delete; 1 = relay (skip to "B" prompt); 2 = Powerline Carrier device (skip
to "A" prompt)
[∗] to continue.
"A" (if X-10 was selected)
UNIT No.
Enter the unit code (01-16, set at the device).
[∗] to return to the Output Number prompt continue
"B" (if relay was selected)
MODULE ADDR
Enter the predefined address for this module (07-15; see Table of Device
Addresses on page 2).
Make sure the module's DIP switches are set to the selected address.
[∗] to continue
REL POSITION (actual relay number on module)
For 4204 modules, relay numbers are 1-4. For 4229 modules, relay
numbers are 1-2.
[∗] to return to the Output Number prompt for programming the next device
∗ ∗ ∗ ∗ 80 Menu Mode
(press ∗ ∗ ∗ ∗ 80 while in Programming mode)
The Output Definition Worksheet is on page 15.
OUTPUT FUNCT. #
Enter the output function number to be defined (VISTA-20P: 01-48;
VISTA-15P: 01-24)). [∗] to continue; 00 = exit
SUMMARY SCREEN
01
A E P Trig
?00 0
0
– ZL=00
This screen displays a summary of the current output programming
A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type
Question mark indicates the device shown has not been mapped. Use *79
Menu mode to map the device.
[∗] to continue
ACTIVATED BY
0 = delete (deletes the output function and any previous programming); a
confirmation prompt appears.
To delete this output definition, press 1. If you do not want to delete this
output, press 0.
1 = zone list (go to "A" prompt); 2 = zone type (go to "B" prompt); 3 = zone
number (go to "C" prompt)
Press [∗] to continue
"A" (if zone list was selected)
ZN LIST
Enter the desired zone list number (01-08). At the ENTER EVENT prompt,
enter the zone list event that will activate this output (0 = restore; 1 = alarm;
2 = fault; 3= trouble)
Press [∗] to continue and skip to the "Output Action" prompt.
"B" (if zone type was selected)
ENTER ZN TYPE
Enter the desired zone type. See list below *80 Worksheet for zone types.
At the PARTITION prompt, enter the partition in which this zone type will
occur (0 = any partition; 1 = partition 1; 2 = partition 2; 3 = partition 3).
Press [∗] to continue and skip to the "Output Action" prompt.
"C"
(if zone number was selected)
ENTER ZN NO.
Enter the desired zone number, then press [∗] to continue. At the ENTER
EVENT prompt, enter the zone event that will activate this output (0 =
restore; 1 = alarm/fault/trouble).
Press [∗] to continue to the OUTPUT ACTION prompt
OUTPUT ACTION
0 = off; 1 = Close for 2 seconds; 2 = Close and Stay Closed; 3 = Continuous
Pulse 1 sec on and 1 sec off
4 = Change Device State; 5 = Duration 1 (see data field *177); 6 = Duration
2 (see data field *177)
Press [∗] to continue.
∗ ∗ ∗ ∗ 80 Menu Mode
(continued)
ENTER OUTPUT NO.
Enter the device output number (programmed in *79 Menu Mode) you want
associated with this output.
01-16 = VISTA-20P output no.; 01-08 = VISTA-15P output no.; 17-18 = on-
board triggers
Press [∗] to continue.
SUMMARY SCREEN
A summary screen appears showing the programmed settings.
Press [∗] to return to OUTPUT FUNCTION NUMBER prompt.
*81 Menu Mode
(press *81 while in Programming mode)
The Zone List Worksheet is on page 14.
ZONE LIST NO.
Enter the zone list number (01-12) to program (or 00 to exit this mode).
Press [∗] to continue.
ENTER ZN NUM.
Enter each zone number (01-64†) to add to the zone list, followed by
pressing [∗] (example, 01∗, 02∗, 03∗).
Press 00 to continue.
† VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
IMPORTANT: Do not include fire zones in zone lists that are used to STOP
device actions.
DEL ZN LIST?
0 = don't delete list; current zone list remains saved
1 = delete this zone list; All zones in the zone list will be deleted.
[∗] to continue
DELETE ZONE?
0 = don't delete zones; save the entire zone list and return to the Zone List
No. prompt
1 = go to next prompt to delete zones
[∗] to continue
ZN TO DELETE?
Enter each zone (01-64†) to be deleted from the list, following each with [∗].
00 when done to return to the Zone List No. prompt.
† VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
*82 Alpha Descriptor Programming
PRE-DEFINED DESCRIPTORS
PROGRAM ALPHA
0 = no (quit Alpha mode)
1 = yes
Press [∗] or [#] to continue.
CUSTOM WORDS
0 = no (continue to descriptor programming)
1 = yes (go to custom word programming)
Press 0 to program standard alpha descriptors. The system will then display
the descriptor for zone 1.
To program custom words, press 1 (custom words are described later).
Press [∗] to continue.
∗ ∗ ∗ ∗ ZN 01
Descriptor screen for zone 1 appears. To program a descriptor (up to 3
words) for a zone, do the following:
1. Press [∗] plus the desired zone number (existing descriptor, if any, is
displayed), then press [∗] plus the zone number again (flashing cursor
appears).
2. a. Press [#] plus the 3-digit number from the Alpha Vocabulary List on
page 11 for the first word.
b. Press [6] to accept the word and move the cursor for the next word.
3. Repeat steps 2a and 2b for the second and third words (if used).
4. When all words have been entered, press [8] to save the descriptor for
that zone. The flashing cursor disappears.
5. Repeat steps 1-4 to assign a descriptor for the next zone.
6. When all descriptors have been entered, press [∗] + 0 + 0 (or simply
press [#]) after the last descriptor has been saved to return to the
PROGRAM ALPHA? prompt.
Enter 0 (no) at the prompt to exit this mode and return to Data Field mode.
– 10 –