Automated Logic G4106 Instrucciones técnicas - Página 4

Navegue en línea o descargue pdf Instrucciones técnicas para Unidad de control Automated Logic G4106. Automated Logic G4106 13 páginas.

7. Verify that there is 24Vac at the power terminals with
a voltmeter.
8.
Turn the G4106's power switch ON and verify that the
module powers up properly.

Communications Wiring

NOTE: ALC recommends using the Network Protection
Board (ALC part no. NWPB) for guarding against
lightning-induced damage.
1.
Check the CMnet wiring for shorts and grounds.
2.
Turn the G4106's power switch OFF.
3.
Terminate the CMnet communications wires to the
G4106 termination strip indicated in Figure 3. Be
sure to follow the same polarity as used throughout
the rest of the CMnet.
4.
Turn the G4106's power switch ON.
5.
Verify communications with the G4106 board (from
the Workstation or from a Direct-Network connected
computer) by requesting a module status (modstat)
using Netscan software.
Rev (29-AUG-97) • Module Driver v4.7

Universal Inputs

A total of 200mA is supplied to these inputs for 4-20mA
transducer wiring. If the total current required by all of the
transducers is greater than 200mA, an additional power
supply is needed. In order to check this, measure the
voltage between the "B" terminal and the ground of the
module. It should read between 18VDC and 24VDC. If it
reads less than 18VDC then the total current required is
greater than 200mA.
The G4106 provides ten universal inputs which are wired
as shown in Figure 4 and 5. These inputs may accept the
following signals.
Thermistor: 10k Ohm @ 77 °F (Precon type 2).
0-5 VDC: The output impedance of a 0-5 VDC source
should not exceed 10k Ohms. The input impedance of the
G4106 module is approximately 1M Ohm.
0-20 mA: 24 VDC loop power, 250 Ohm input
impedance.
NOTE: For a 4-20 mA passive transducer having 12V
loop input, place a 10 V, 1 W Zener diode (1N4740A) in
series with the sensor as shown in Figure 5. Without the
diode the sensor circuitry could overheat when connected
to the 24 VDC supplied by the module, causing false high
readings.
Figure 3: Wiring power and communications
4
© 1995-97 Automated Logic Corporation