U niver sal In p u t
M o d e Sel ect
Figure 5. Jumper Position
compare it to the condition reported on
the FB's Status page.
Digital Outputs
The M220nx module has two digital outputs
which can be connected to a maximum of 24
Volts AC/DC. Each output is a dry contact
(rated at 3A maximum) that is normally open.
Be sure the M220nx's power is off before
wiring any inputs or outputs. Connect the
output wiring to the screw terminals on the
module as shown in Figure 6.
B
A
B
A
Figure 6. Digital Output Wiring
NOTE
Do not power pilot relays from the
same transformer that powers the M220nx.
To verify each output's operation, lock the
output to a known condition using the
Function Block's Parameter page, then make
sure the equipment actually operates as
specified.
Each digital output can be placed in Manual
or Auto mode by setting the HOA switches
Revised 4/3/00 • M220nx
Grip
H er e
D R Y
C O N T A C T
2 4 V A C
(see Figure 1 on page 2 for the switches'
location). You can monitor the status of the
HOA switches through SuperVision by
assigning each switch a digital input in the FB
using channel numbers 81 and 82.
An off status on these channels means the
HOA switch is in Auto mode. An on status
means the HOA switch is in Manual mode.
Channel Numbers
The following tables show the valid channel
numbers for each point on the M220nx. Enter
the channel number, offset, and gain for each
point in Eikon before the Function Block is
made, or on the FB's Parameter page in
SuperVision. If an offset and gain are not
provided here, use SuperVision's Point
Configuration or Point Help feature to
determine the offset and gain.
Table 3. Input Channel Numbers
Channel
Point
Signal Type
Number
Thermistor
31
UI 1
mA or Volts
31
Digital
21
Thermistor
32
UI 2
mA or Volts
32
Digital
22
† Celsius values can only be displayed in SuperVision when the Function
Block is made in Eikon v2.0 or later with the Metric option enabled. Refer to
the Eikon User's Guide for more information.
§ Use the Point Configuration or Point Help feature in SuperVision v2.0 or
later.
Table 4. Digital Output Channel Numbers
Channel
Point
Signal Type
Number
Digital
11
DO 1
HOA Status†
81
Digital
12
DO 2
HOA Status†
82
† Use a digital input microblock to
monitor the status of HOA Switches.
7
© 2000 Automated Logic Corporation
†Range
Offset
Gain
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V