ADEMCO VISTA-15P Manual de programación - Página 3

Navegue en línea o descargue pdf Manual de programación para Sistema de seguridad ADEMCO VISTA-15P. ADEMCO VISTA-15P 17 páginas. Programming auto arming and disarming schedules
También para ADEMCO VISTA-15P: Manual de instalación rápida (2 páginas), Manual del usuario (20 páginas), Manual de programación (17 páginas), Manual de instalación rápida (2 páginas), Manual de instalación rápida (2 páginas), Manual de programación (2 páginas), Manual rápido (2 páginas)

ADEMCO VISTA-15P Manual de programación
Entries apply to the ADEMCO VISTA-15P/VISTA-15PSIA and ADEMCO VISTA-20P/VISTA-20PSIA controls, except entries shown in dashed
boxes, which apply only to the VISTA-20P/VISTA-20PSIA (partition entries) and are not applicable to the VISTA-15P/VISTA-15PSIA. In addition,
where noted, certain fields have special settings when used with the VISTA-20PSIA/VISTA-15PSIA (indicated by
borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines: Notes in certain fields give instructions for programming the VISTA-20P/VISTA-15P for False Alarm Reduction.
∗ ∗ ∗ ∗ 20
Installer Code
4 digits, 0–9
∗ ∗ ∗ ∗ 21
Quick Arm Enable
0 = no; 1 = yes
∗ ∗ ∗ ∗ 22
RF Jam Option
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
∗ ∗ ∗ ∗ 23
Quick (Forced) Bypass
0 = no quick bypass UL: must be "0"
1 = allow quick bypass (code + [6] + [#] )
∗ ∗ ∗ ∗ 24
RF House ID Code
00 = disable all wireless keypad usage
01–31 = using 5827, 5827BD or 5804BD keypad
∗ ∗ ∗ ∗ 26
Chime By Zone
0 = no; 1 = yes (list chime zones on zone list 3 using *81 Menu mode)
∗ ∗ ∗ ∗ 27
Powerline Carrier Device (X–10)

House Code

0 = A; 1 = B; 2 = C; 3 = D; 4 = E; 5 = F; 6 = G; 7 = H; 8 = I; 9 = J;
#10 = K; #11 = L; #12 = M; #13 = N; #14 = O; #15 = P
UL: not for fire or UL installations
∗ ∗ ∗ ∗ 28
Access Code For Phone Module
00 = disable;
1st digit: enter 1–9; 2nd digit: enter # + 11 for " ✱ ", or # + 12 for "#".
UL: must be "00" for UL Commercial Burg. installations
∗ ∗ ∗ ∗ 29
Long Range Radio Output
0 = disable; 1 = enable
∗ ∗ ∗ ∗ 31
Single Alarm Sounding Per Zone
0 = unlimited sounding; 1 = one alarm sounding per zone
V20PSIA/V15PSIA:
If "0" selected, "alarm sounding per zone" will be
the same as the "number of reports in armed period" set in field *93 (1
if one report, 2 if 2 reports, unlimited for zones in zone list 7).
∗ ∗ ∗ ∗ 32
Fire Alarm Sounder Timeout
0 = sound stops at timeout; 1 = no timeout UL: must be "1" for fire install.
∗ ∗ ∗ ∗ 33
Alarm Sounder (Bell) Timeout
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
∗ ∗ ∗ ∗ 34
Exit Delay
00 - 96 = 0 - 96 secs; 97 = 120 secs
SIA Guidelines: minimum exit delay is 45 seconds
V20PSIA/V15PSIA:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-second delay.
UL: see inst. instr. for requirements.
∗ ∗ ∗ ∗ 35
Entry Delay #1
Common zones use same delay as partition 1.
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
SIA Guidelines: minimum entry delay is 30 seconds
V20PSIA/V15PSIA:
30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-second delay.
For UL Residential Burglary Alarm installations, must be set for a
maximum of 30 seconds; entry delay plus dial delay should not
exceed 1 min. For UL Commercial Burglar Alarm, total entry delay
may not exceed 45 seconds.

PROGRAMMING FORM

[4112]
|
|
|
[0,0]
Part. 1 Part.2
[0,0]
Part. 1 Part. 2
|
|
[00,00,00]
Part. 1 Part. 2
Common
[0]
[0]
[00]
|
(Partition 1 only)
[0]
[0]
[0]
[1]
[60,60]
|
Part. 1
Part. 2
Common zones use part. 1 delay.
[30,30]
|
Part. 1
Part. 2
∗ ∗ ∗ ∗ 36
Entry Delay #2
See *35 Entry Delay 1 for entries.
∗ ∗ ∗ ∗ 37
Audible Exit Warning
0 = no; 1 = yes (SIA Guidelines: must be enabled)
V20PSIA/V15PSIA:
[0]
∗ ∗ ∗ ∗ 38
Confirmation Of Arming Ding
0 = no; 1 = yes (wired keypads and RF)
2 = yes, RF only
UL: must be "1" for UL Commercial Burglar Alarm inst.
∗ ∗ ∗ ∗ 39
Power Up In Previous State
|
0 = no, always power up disarmed; 1 = yes, power up in previous state
UL: must be "1" SIA Guidelines: must be "1"
DIALER PROGRAMMING ( ✱ 40 – ✱ 42)
Do not fill unused spaces. Enter 0–9; #+11 for ' ✱ '; #+12 for '#'; #+13 for a 2-
second pause. If fewer than the maximum digits entered, exit the field by
pressing [✶]. The next data field number is displayed.
∗ ∗ ∗ ∗ 40
PABX Access Code or
Call Waiting Disable
press ✱40✱. If call waiting is used, enter call waiting disable digits "∗
(#+11) 70" plus "# + 13" (pause).
NOTES: 1. The call waiting disable feature cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call waiting line will
prevent successful communication to the central station.
V20PSIA/V15PSIA:
as described above, and also set Call Waiting Disable option in field *91.
∗ ∗ ∗ ∗ 41
Primary Phone No.
|
|
|
|
∗ ∗ ∗ ∗ 42
Second Phone No.
|
|
|
|
Enter up to 20 digits. To clear entries, press ✱ 41 ✱ or ✱ 42 ✱ respectively .
NOTE: For fields *43 thru *46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D;
#+14 for E; #+15 for F. Enter [ ✱ ] as the fourth digit if a 3-digit account number
(for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are
used. E.g., For Acct. B234, enter: #+11 + 2 + 3 + 4
∗ ∗ ∗ ∗ 43
Partition 1 Primary Acct. No.
| | | /
| | | | |
chosen in *48 Report Format. See box above. To clear entries, press * 43 *.
∗ ∗ ∗ ∗ 44
Part. 1 Secondary Acct. No.
| | | /
| | | | |
|
∗ ∗ ∗ ∗ 45
Partition 2 Primary Acct. No.
| | | /
| | | | |
∗ ∗ ∗ ∗ 46
Partition 2 Secondary Acct. No.
| | | /
| | | | |
∗ ∗ ∗ ∗ 47
Phone System Select
If Cent. Sta. is not on a WATS line: 0=Pulse Dial; 1=Tone Dial;
|
if Cent. Sta. is on a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
∗ ∗ ∗ ∗ 48
Report Format
0 = 3+1, 4+1 ADEMCO L/S STANDARD
1 = 3+1, 4+1 RADIONICS STANDARD
2 = 4+2 ADEMCO L/S STANDARD
3 = 4+2 RADIONICS STANDARD
5 = 10-digit ADEMCO CONTACT ID® REPORTING
6 = 4+2 ADEMCO EXPRESS
7 = 4-digit ADEMCO CONTACT ID® REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXPANDED
9 = 3+1, 4+1 RADIONICS EXPANDED
– 3 –
V20PSIA/V15PSIA
[30,30]
Part. 1
[1,1]
feature always enabled; field does not exist
[0,0]
Enter up to 6 digits. To clear entries,
If call waiting is used, enter call waiting disable digits
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
[FFFFFFFFFF] Enter 4 or 10 digits, as
(see field *43 for entries)
[FFFFFFFFFF] To clear, press * 44 * .
(see field *43 for entries)
[FFFFFFFFFF] To clear, press * 45 * .
(see field *43 for entries)
[FFFFFFFFFF] To clear, press * 46 * .
[77]
primary secondary
with heavy
|
|
Part. 2
Part. 1 Part. 2
Part. 1 Part. 2
[1]
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
[1]