DynaGen GSC400 Series Manual de la Utilidad de Calibración - Página 12
Navegue en línea o descargue pdf Manual de la Utilidad de Calibración para Controlador DynaGen GSC400 Series. DynaGen GSC400 Series 18 páginas. For generator
También para DynaGen GSC400 Series: Manual del programador (4 páginas)
3.3.2 Wizard Walk Through
This section will walk you though the wizard steps so you'll know what to expect.
During the calibration you will be required to measure the load current and enter
it into the wizard. Ideally the load current should be steady to obtain a good
calibration but if not you can try averaging the current readings.
1. At the welcome screen click Next.
You will see the window to the
right.
If you are doing a current only
calibration enter any non-zero
number into the boxes for the
phases that the GSC400 senses.
If you are doing a voltage
calibration you will need to
measure the voltage for each
phase and enter it into each box (it is
important that you enter zero for the
phases not sensed by the GSC400 or the wizard will attempt
calibration for that phase).
Click Next.
2. You will be asked to place the
controller in the OFF mode. You can
ignore this for GSC400 firmware
versions 2.00 and above.
Press OK.
The Utility will get the CT ratio.
12 of 18
Figure 7
Figure 8