Step 2: Connect Switches to Input Terminals
To complete this quick-start exercise or use other examples in this manual, you'll need to either
connect some input switches as shown below or install the F0-08SIM, a simulator module
which needs no wiring, into the option slot. If you have DC inputs you will need to use the
FA–24PS (24VDC) or an alternative external 12-24VDC power supply. Be sure to follow the
instructions in the accompanying WARNING note.
–
12–24VDC
Power Supply
D0–05AR, D0–05AD, D0–05AA
(AC input versions, 120V AC only)
X0 - X7: Input
T
oggle Switches, UL Listed
(User provided)
D0-O5DR, D0-05DD, D0-05DA
D0-05DR-D, D0-05DD-D
(DC input versions, 12-24VDC)
X0 - X7: Input
Y0 - Y5: Output
C3
DL05 Micro PLC User Manual, 6th Edition, Rev. E
Chapter 1: Getting Started
Y0 - Y5: Output
Toggle Switches, UL Listed
(User provided)
WARNING: DO NOT wire the
toggle switches as shown to
240VAC-powered units. The
discrete inputs will only accept
120VAC nominal. Also, remove
power and unplug the DL05 when
wiring the switches. Only use
UL-approved switches rated for at
least 250VAC, 1A for AC inputs.
Firmly mount the switches before
using.
1-7