Smoke & Heat Detector Troubleshooting
4. Wait at least 20 seconds to ensure proper power-down sequence.
5. Remove the detector cover by turning counter-clockwise.
6. Vacuum the cover or use canned air to remove any dust or debris.
7. Remove the top half of the screen/sensing chamber by lifting straight up.
8. Vacuum or use canned air to remove any dust or particles that are present on all chamber sections.
9. Replace the top half of the screen/sensing chamber by aligning the arrow on the screen/sensing
chamber with the arrow on the housing. Press down firmly until the screen/sensing chamber is fully
seated.
10. Replace the detector cover by placing it over the screen/sensing chamber and turning it clockwise
until it snaps into place.
11. Reinstall the battery into the battery compartment noting proper orientation. The red and green
LEDs will flash once every 5 seconds for approximately 20 seconds until the power-up cycle is
complete.
12. Reinstall the detector housing onto the base.
13. Test the smoke detector. Please refer to Testing the Smoke Detector below.
14. Remove your system from Test mode. Please refer to the
https://alpha.adt.com/help/89[11/12/2018 9:58:31 PM]
System Test
page.