ADEMCO 4192CP Instalación y mantenimiento

Navegue en línea o descargue pdf Instalación y mantenimiento para Alarma de humo ADEMCO 4192CP. ADEMCO 4192CP 4 páginas. Addressable ionization smoke detector

~
INSTALLATION AND MAINTENANCE
INSTRUCTIONS FOR MOOEL 4192CP
AOORESSABLE IONIZATION SMOKE DETECTOR
Sefore i"stal fin detectors, please thoroughly read the Vec!or/VisttiMi niscan system installation instruc.
t
fiOnS, a nd the anual 156:210-00(the domestic Applications Man"al for System Smoke De18ctor~]~~ch
provide detaded information on detector Spac]n placement, zones ands ecial applications. Copies of
!'
P
these manuals are available from ADEMCO. N PA 72E and NEMA guide Ines should also be obsewed,
GENERAL DESCRIPTION
The model 4192CP dual-chamber ionization smoke detectors utifize a state of the ati unipolar sensing
chamber. These defectors aredesigned toprovlde openarea protection, andtobe usedwith compatible
UL-hsted Ademcocontrol panels only. (See note, t page 3).
PHVSICAL AND ELECTRICAL
SPECIFICATIONS
Sase Diametec
5.0 inches
(12.7cm)
Cover Height
3.0 inches
(7.6 cm)
Cover Dlamotex
3.t5inches
(8cm)
Voltage Range:
7-11 VDC (with t KHz of modulation)
Standby Current (mm.):
320 microamps
Alarm Current Range:
230 mlcroamps min. 400 microamps mx.
Operating Temperature Range:
0° to 49°C (32°t20"F)
MOUNTING
INSTRUCTIONS
Each 4192CP sehes detector unit is supp~ed with a mounting bracket Kt that permits the detector to be
mounted using several dfterent techniques:
1. Units may bemo"nted
direcOytoa3.inch
or4-inch oclago" box, l-t/2 inches deep (No, 1z50,
equivalent) electrical box using the suppbed mounting bracket (See figures 1 and 2),
2. Units may bemo"ntedto
84-inch square electrical box by"sing aplaster ring wi!hfhes"pplied
mounting bracket,
3, Units may bemou"ted ~rectly to!heceifing using theplastic sc,ewanchor$ packed wifhthebrack.
et. For direct mounting, the bracket is used asatemplat@and 3116 inch holes aredrilledlor
the
screw anchors.
Figure 1. F1.sh Mou,,ti.gof
figu,e2.
Detector Mounting
Detector on Octagon Box
Bracket
WIRING INSTALLATION
GUIDELINES'
All widng Must be installed in Gompfia"cewith the National Electrical Code, local codes, a"d the authority
having jurdsdction, Proper wire gauges should be"sed, Theconduclor$ usedtoconr!ect smoke detec.
torstothe control pan81should becolor-coded toprevent witing mistakes. Improper connections can
prevent a system from responding properly in the event of a fire,
m...
"o
".
.,
,.
..."
.
.