Automationdirect.com Productivity 2000 P2-8AD4DA-1 Manual - Página 3
Navegue en línea o descargue pdf Manual para Sistemas de E/S Automationdirect.com Productivity 2000 P2-8AD4DA-1. Automationdirect.com Productivity 2000 P2-8AD4DA-1 8 páginas. Analog input/output
Wiring Diagram
Current Input Circuits
–
2-Wire 4-20 mA
Transmitter
+
2-Wire Transmitter
+
+
3-Wire Current
Transmitter
–
3-Wire Transmitter
+
4-Wire 4-20 mA
Transmitter
–
User Supplied
AC or DC
Transmitter Power
4-Wire Transmitter
Note: Do not connect both ends of shield.
Current Output Circuits
4 - 20mA
Load
Note: Shield is connected to common at the source device.
Sales 800-633-0405
An Edison S500-32-R
0.032A fast-acting fuse
fuse
is recommended for all
.032A
4-20 mA current loops.
+
–
+24VDC User
Supplied Power
fuse
.032A
COM
+ –
+24VDC User
Supplied Power
fuse
.032A
Schematic
COM
I1+
I2+
I3+
I4+
I5+
I6+
I7+
I8+
COM
I1+
I2+
I3+
I4+
COM
COM
0V
-
+
24V+
24 VDC User
Supplied Power
Note: This module includes input and output channels. Before connecting
eld wiring, verify that you are connecting to the appropriate terminals
www.productivity2000.com
INTERNAL
MODULE CIRCUITRY
CH1 ADC
CH2 ADC
CH3 ADC
CH4 ADC
CH5 ADC
CH6 ADC
CH7 ADC
CH8 ADC
CH1 DAC
CH2 DAC
CH3 DAC
CH4 DAC
ISOLATED ANALOG
CIRCUIT POWER
ISOLATED ANALOG
CIRCUIT COMMON
7