Automationdirect.com Stride SIO-MB04THMS Manual de inicio rápido

Navegue en línea o descargue pdf Manual de inicio rápido para Sistemas de E/S Automationdirect.com Stride SIO-MB04THMS. Automationdirect.com Stride SIO-MB04THMS 2 páginas. Field i/o modules, temperature input module: thermocouple, 4-channel in

Automationdirect.com Stride SIO-MB04THMS Manual de inicio rápido
T
eMperaTure
FEATURES
• Interface Ethernet 10/100 Base-T, Modbus TCP Server
• 4 isolated input channels
• Each input configurable for mV or Tc
• Integrated web server to acquire the status of the analog inputs via browser
• Remotely configurable
• Connection by removable screw terminals
• LED signaling for Link/Act Ethernet, power supply
• Galvanic isolation
• UL listed / CE mark
• In compliance with EN-50022 DIN rail mounting
GENERAL DESCRIPTION
The SIO-MB04THMS device is a Modbus TCP server that can convert up to 4 analog signals applied to the inputs into engineering units in digital format.
The inputs can be connected to thermocouples or sensors having mV output.
The input channels are electrically isolated from each other.
The device guarantees high accuracy and a stable measurement versus time and temperature. The device is equipped with a selectable Watchdog Timer
system. The Ethernet interface allows reading and writing the values of the internal registers of the device in real time.
Signal LEDs for Ethernet activity and power supply allow direct monitoring of the system.
The built-in Web Server allows remote visualization, acquisition of the analog inputs and access to the configuration parameters.
Connections are made by removable screw terminals (inputs and power supply) and RJ45 plug (Ethernet).
The SIO-MB04THMS is in compliance with Directive UL 61010-1 for the US market and with Directive CSA C22.2 No 61010-1 for the Canadian market.
The device has full electrical isolation between the lines, providing protection against the effects of ground loops existing in industrial applications.
It is housed in a tough self-extinguishing plastic enclosure which, thanks to its thin 22.5 mm profile, allows high-density mounting on EN-50022 standard DIN rail.
USER INSTRUCTIONS
Before installing the device, please read the "Installation Instructions" section.
To configure the device in INIT mode, refer to the User Guide. Connect power supply, Ethernet and analog inputs as shown in the "Wiring" section. The LED
states indicate the working condition of the device; see the "Front Panel LEDs" table to verify the device working state.
Instructions for configuration and calibration operations are contained in the User Guide.
To simplify handling or replacing of the device, it is possible to remove the wired terminals even with the device powered.
NETWORK CONNECTIVITY
Standard
In compliance with IEEE 802.3
Network Interface
Ethernet 10/100Base-T
Protocol
Max. Cable Length
Number of Sockets
16 simultaneous Modbus TCP connections
INPUTS
Input Type
Min
Voltage
mV
-250mV
Thermocouple
J
-210°C
K
-210°C
R
-50°C
S
-50°C
B
+400°C
E
-210°C
T
-210°C
N
-210°C
Please refer to the User Guide for more information, including the
compete Modbus address list. Access the user guide by visiting
https://www.automationdirect.com/pn/doc/manual/SIO-MB04THMS
or scan the QR code below.
®
S
®
tride
i
M
:
npuT
Odule
TherMOcOuple
TECHNICAL SPECIFICATIONS (typical @ 25°C, nominal conditions)
Input Accuracy (1)
Modbus TCP
Linearity (1)
100m [328ft]
Max. Cold Junction Compensation
Error (CJC)
Max
Input Impedance
+250mV
Lead Wire Resistance
Influence(1)
+1200°C
Thermal Drift (1) Full Scale
+1372°C
+1767°C
Thermal Drift (CJC) Full Scale
+1767°C
Sampling Time
+1825°C
Warm-up Time
+1000°C
+400°C
(1) Referred to input Span (difference between maximum and minimum values).
+1300°C
F
i/O M
ield
, 4-
channel in
I/O SPECIFICATIONS
The greater of
±0.05% full scale
and ±5μV
mV
±0.1% full scale
Tc
±0.2% full scale
±2°C
mV
≥ 1MΩ
Tc
mV
< 0.8 μV/Ohm
Tc
±0.005%/°C
±0.02%/°C
150ms (4 channels)
3 min.
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860, USA
Odules
(pn# siO-MB04ThMs)
POWER SUPPLY
Power Supply Voltage
Reverse Polarity Protection
Current Consumption
ISOLATION
Power Supply / Ethernet
Inputs / Power Supply
Inputs / Ethernet
Input / Input
ENVIRONMENTAL CONDITIONS
Operating Temperature
UL Operating Temperature
Storage Temperature
Humidity (non-condensing)
Maximum Altitude
Installation
Pollution Degree
CONNECTIONS
Ethernet
Inputs / Power Supply
MECHANICAL SPECIFICATIONS
Material
IP Code
Wire diameter
Tightening Torque
Mounting
Weight
EMC (for industrial environments)
Immunity
Emission
US Standard
Canadian Standard
CCN
UL Type Designation
Classification
File Number
14–30VDC
To maintain a UL 508 panel listing use a
Class 2 power supply.
60VDC max
150mA max (2)
1500VAC, 50Hz, 1 min
1500VAC, 50Hz, 1 min
1500VAC, 50Hz, 1 min
1500VAC, 50Hz, 1 min
-10°C to +60°C [+14°F to +140°F]
-10°C to +40°C [+14°F to +104°F]
-40°C to +85°C [-40°F to +185°F]
0 to 90%
2000m [6500ft]
Indoor
2
RJ-45
Removable screw terminals
Self-extinguishing plastic
IP20
0.8 to 2.1 mm
/ AWG 14–18
2
0.5 N·m [4.4 in·lb]
In compliance with DIN rail standard EN-50022
About 160g [5.6 oz]
EN 61000-6-2
EN 61000-6-4
UL
UL 61010-1
CSA C22.2 No 61010-1
NRAQ/NRAQ7
Open Type device
Industrial Control Equipment
E157382