ADEMCO 5707 Manual de instrucciones de instalación - Página 3

Navegue en línea o descargue pdf Manual de instrucciones de instalación para Alarma de humo ADEMCO 5707. ADEMCO 5707 12 páginas. Smoke detector with built-in wireless transmitter

ADEMCO 5707 Manual de instrucciones de instalación
BAITERY
INSTALLATION
1. The detectot% battery compartment
cover/mounting
bracket should have been
removed, as previously indicated.
See Figure 3.
2. Install two fresh Duracell MN 1604, 9-volt alkaline batteries
in their correct
positions in the detector's battery compartment.
Be sure to observe correct
polarity, and do not force the batteries into the compartment.
The detector%
LED indicator should flash once every 7 seconds, indicating normal operation.
If the batteries are not installed correctly, the smoke detector will not function.
If the unit appears
not to be sending
a signal during any of the tests that
follow, check for correct battery installation.
L
INSERT
S(
'VER
IN HERE AND TWIST
TO RELEASE
COVER
-9
VOLT ALKALINE
Figure 3.
Bottom View
of Smoke Detector
(mounting
bracket removed)
MOUNTING
THE SMOKE
DETECTOR
First, determine
the best location
for the smoke detector
(one that provides
strong wireless transmission
paths AND proper smoke detector protection).
See
NFPA
RECOMMENDATIONS
REGARDING
SMOKE
DETECTOR
INS TALLA TION
and
RECOMMENDED
LOCATIONS
FOR
SMOKE
DETECTORS
(on a following
page). A good RF transmission
path must be
established
from the proposed
mounting
location before permanently
installing
the detector. To check, perform the test in
Wre/ess TramnissioII Path Test.
Sstsctlng Mounting
Locations
Detectors should be located as close to the center of the ceiling as possible. If
this is not practical, detectors maybe located on the ceiling up to 4 inches (1Ocm)
from the ceiling-wall
junction.
Do not install
near forced
air heating
or air
conditioning
ducts
(outlets
or returns).
For sloped,
gabled
or high-peaked
ceilings, detectors must be mounted between 4 and 6 inches (1 O and 15cm) f mm
the highest point in the ceiling.
Detectors may also be wall-mounted
if permitted by local and state codes. Check
with your
local
Fire Department
about
code
requirements.
Wall-mounted
detectors should be located 4-6 inches (1 O-15 cm) from the ceiling. In mobile
homes,
battery-operated
detectors
are
not
generally
installed
by the
manufacturer.
Mount detectors ONLY on an inter"kx wall.
-3-