OPERATING CONDITIONS

The fan is rated and designed for S1 (IEC 60034-1) continuous operation.
Extreme ON-OFF switching operating must be avoided, because it has negative influence on life expectancy and power consumption.
Cycling operating mode should only with cycling ON/OFF via control signal (0/10V analog input or PWM input).
Do not cycling the power supply for cycling operating mode – use control signal ! High 'In-rush current' can occur during cycling power supply!
Permissible ambient temperature is stated to the specified operating points. If actual load deviates from specified operating point, motor
temperature-rise should be checked.
Figures on the motor name-plate refer to nominal values according to EN 60335 if not otherwise specified and inscribed on the nameplate (EN
60335, 'free air', 'max.load', 'max.eff.', cust. unit / cust. spec., UL, IEC 60034-1)
Continuous sound pressure level may exceed 70dBA (depends of fan model).
If an already installed fan is switched OFF for a long period in a humid atmosphere, it should be switched ON for minimum of two hours every
month to remove any moisture that may have condensed inside the motor.
Protection (motor & electronics): IP54 according to EN60529 when it is installed in the customer's application. At least IP10 level of protection
must be provided with application enclousure.
Power consumption in stand-by mode: les than 1.0W acc. to EN 50561.
NOMINAL DATA - defined according to ' MAX. LOAD '
Phase : 1~
Voltage : 230 V
Frequency : 50-60 Hz
Input power: 300 W
Nominal current : 2 A
Rotational speed : 1100 RPM
Max. ambient temperature : 65 °C
Degree of protection provided by enclosures : IP54
Insulation class : 130
Min. ambient temperature : -25 °C
Max. pressure : 80 Pa
ErP DATA
Overall Efficiency , Effes : 49 %
Installation category : A
Efficiency category : static
Efficiency grade , N : 58,5
Variable speed drive : INTEGRATED
Power Input , Pelec: 317,5 W
Airflow volume , qV: 4691 m³/h
Pressure Increase, ps: 111 Pa
Rotational Speed, n : 1110 RPM
Specific ratio : 1,001
Airflow volume max. , qV: 7218 m³/h
Pressure Increase max., ps: 177 Pa
© Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
USER'S GUIDE R10 AXIAL FAN , Code: 0000, Iss: 9.07.2019
An example of a label and explanation of the content:
1
3
2
8
7
1. Fan type and code
2. Trade mark and manufacturer address
3. Nominal values (Voltage, frequency, Electric Power, Current...)
4. Certification marks
5. Date of production (week of the year/year)
6. QR code which includes code number, production date, serial number and
link to website.
7. Data acc. to EU regulation 327/2011 (ErP)
8. NOTE INDICATE TO WHICH STANDARD/RULES CORESPOND DATA ON THE
NAMEPLATE:
- EN 60335-1 : Name-plate data are made according to standard EN 60335-
1, Household and similar electrical appliances – Safety – Part 1 :
10.1 If an appliance is marked with rated power input, the power input at
normal operating temperature shall not deviate from the rated power
input by more than: + 20% if Pn<300W or +15% (or 60W whichever is the
greater) if Pn>300W.
10.2 If an appliance is marked with rated current, the current at normal
operating temperature shall not deviate from the rated current by more
than: +20% if In<1.5A or +15% (or 0,30A whichever is the greater) if
In>1.5A.
- FREE AIR : Data on the nameplate established at a point 0Pa static
pressure.
- MAX LOAD : Data on the nameplate established at a point of maximal
static pressure regarding max. ambient
- MAX. EFF. : Data on the nameplate established at a point of maximal
static efficiency.
- CUST. UNIT / CUST. SPEC. : Data on the nameplate specified according to
customer specifications or at working point in customer's unit .
- UL - Data on the nameplate defined according to specifications in UL
standards.
- IEC 60034-1 - Data on the nameplate established at a point of nominal
load according to standard for Rotational electrical machines.
4
5
6
temperature
.
4 / 8