Navegue en línea o descargue pdf Folleto de programación e instalación para Instrumentos de medida Autometers Systems A-400MB. Autometers Systems A-400MB 17 páginas. Mid approved sgs.uk appendix b and d, measures kwh, kvarh, kvar,pf,hz, max demand, rs 485 modbus autometers v6 protocol, two pulse outputs, bi- directional measurement for import and export, back light lcd for full viewing angles, available as 1 phase 2 w

Introduction
This document provides operating,
maintenance and installation
instructions.These units measure and
display the characteristics of single phase
two wires (1p2w),three phase three wires
(3p3w) and three phase four wires
(3p4w) networks.The measuring
parameters include voltage (V),
frequency (Hz),current (A),power
(kW/kVa/kVar),import, export and total
Energy (kWh/kVarh).The units can also
measure Maximum demand current and
power, this is measured over preset
periods of up to 60 minutes.
The A-400 range of meters are 100 amp
maximum direct connected meters and
can be supplied in two versions, with the
mains supply entering at the top of the
meter or the mains supply entering at
the bottom of the meter.
The meters can also be supplied with
different communication outputs
Modbus RS 485, MBus or two individual
Pulse outputs one programmable.
1
Declaration of
Conformity
We, Autometers Systems Ltd, 4B Albany
Road, Manchester, M21 0AW, UK ensure
and declare that apparatus: Energy Meter:
A-400P, A-400M, A-400MB,A-400MT with
the measurement range 3x230/400V
0,25~5(45) A 50Hz are in conformity with
the type as described in the EU-type
examination certificate 0120/SGS0350 with
Serial number in format of XXXXXXXX, Batch
format: xxxxxx and satisfy the appropriate
requirements of the Directive 2014/32/EU
with the following standards: EN 50470-1:
2006, Electricity metering equipment (AC)
Part 1: General requirements, tests and test
conditions. Metering equipment (class
indexes A, B and C) and EN 50470-3: 2006,
Electricity metering equipment (AC) Part 3:
Particular requirements - Static meters for
active energy (class indexes A, B and C)