PID Type
Select the mode depending on the characteristics of the control target by refering to
the following desciption.
High speed response mode
Temp.
S
SV
PV
t
Time
Used to minimize the time (t) required to
reach the SV. Overshoot (S) occurs. Used in
machinery that may require warming up.
(injection molding machine, electric furnace,
etc.)
Low speed response mode
Temp.
SV
PV
t
Time
Used to minimize overshoot (S). Time (t)
required to reach SV may be slower.
Used for machinery or environments where
overshoot may cause explosion or fire. (oil
temperature control, metal plating machinery,
etc.)
Function: Alarm
Set both alarm operation and alarm option by combining.
88* 8
Each alarm operates individually in two alarm output models.
Alarm
Alarm
When the current temperature is out of alarm range, alarm clears
operation
option
automatically.
■ Operation
Name
Alarm operation
-
-
OFF
H
ON
Deviation
SV
PV
high limit
100℃
110℃
High deviation: Set as 10℃ High deviation: Set as -10℃
ON
H
OFF
Deviation
PV
SV
low limit
90℃
100℃
Low deviation: Set as 10℃
ON
H
OFF
Deviation
high, low
PV
SV
90℃
100℃
limit
High, Low deviation: Set as 10℃
OFF
H
ON
Deviation
high, low
PV
SV
90℃
100℃
limit reverse
High, Low deviation: Set as 10℃
OFF
H
ON
Absolute
value high
PV
SV
90℃
100℃
limit
Absolute value: Set as 90℃ Absolute value: Set as 110℃
ON
H
OFF
Absolute
value low
PV
SV
90℃
100℃
limit
Absolute value: Set as 90℃ Absolute value: Set as 110℃
Sensor break -
Loop break
-
■ Option
Name
Description
Standard
If it is an alarm condition, alarm output is ON. If it is a clear alarm
alarm
condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON and maintains ON
Alarm latch
status.
First alarm condition is ignored and from second alarm
Standby
condition, standard alarm operates. When power is supplied
sequence
and it is an alarm condition, this first alarm condition is ignored
and from the second alarm condition, standard alarm operates.
Alarm
If it is an alarm condition, it operates both alarm latch and
latch and
standby sequence. When power is supplied and it is an alarm
standby
condition, this first alarm condition is ignored and from the
sequence
second 1alarm condition, alarm latch operates.
Segment Table
The segments displayed on the product indicate the following meanings. It may differ
depending on the product.
7 Segment
11 Segment
0
I
0
0
0
I
1
J
1
1
1
J
2
K
2
2
2
K
3
L
3
3
3
L
4
M
4
4
4
M
5
N
5
5
5
N
6
O
6
6
6
O
7
P
7
7
7
P
8
Q
8
8
8
Q
9
R
9
9
9
R
A
S
A
A
A
S
B
T
B
B
B
T
C
U
C
C
C
U
D
V
D
D
D
V
E
W
E
E
E
W
F
X
F
F
F
X
G
Y
G
G
G
Y
H
Z
H
H
H
Z
18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002
www.autonics.com | +82-2-2048-1577 | [email protected]
• H: Alarm output hysteresis
Description
No alarm output
If deviation between PV and
OFF
H
ON
SV as high-limit is higher
PV
SV
than set value of deviation
90℃
100℃
temperature, the alarm
output will be ON.
If deviation between PV
ON
H
OFF
and SV as low limit is higher
than set value of deviation
SV
PV
100℃
110℃
temperature, the alarm
Low deviation: Set as -10℃
output will be ON.
If deviation between PV
H
ON
and SV as high/low-limit
is higher than set value of
PV
110℃
deviation temperature, the
alarm output will be ON.
If deviation between PV and
H
OFF
SV as high/low-limit is lower
than set value of deviation
PV
110℃
temperature, the alarm
output will be OFF.
OFF
H
ON
If PV is higher than the
absolute value, the output
SV
PV
100℃
110℃
will be ON.
ON
H
OFF
If PV is lower than the
absolute value, the output
SV
PV
100℃
110℃
will be ON.
It will be ON when it detects
sensor disconnection.
It will be ON when it detects
loop disconnection.
12 Segment
16 Segment
I
0
I
0
I
0
I
0
I
J
1
J
1
J
1
J
1
J
K
2
K
2
K
2
K
2
K
L
3
L
3
L
3
L
3
L
M
4
M
4
M
4
M
4
M
N
5
N
5
N
5
N
5
N
O
6
O
6
O
6
O
6
O
P
7
P
7
P
7
P
7
P
Q
8
Q
8
Q
8
Q
8
Q
R
9
R
9
R
9
R
9
R
S
A
S
A
S
A
S
A
S
T
B
T
B
T
B
T
B
T
U
C
U
C
U
C
U
C
U
V
D
V
D
V
D
V
D
V
W
E
W
E
W
E
W
E
W
X
F
X
F
X
F
X
F
X
Y
G
Y
G
Y
G
Y
G
Y
Z
H
Z
H
Z
H
Z
H
Z
-
Condition
of re-apply
-
-
Power ON
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z