Autonics TR1D-14RN Manual - Página 5
Navegue en línea o descargue pdf Manual para Controlador de temperatura Autonics TR1D-14RN. Autonics TR1D-14RN 6 páginas. Independent single display pid temperature controllers

■ Parameter 2 group
Parameter
Display Default Setting range
2-1
Input specification
KCaH Refer to 'Input Type and Using Range'
IN-T
2-2
Temperature unit
?C ℃, ℉
UNIT
2-3
Sampling period
50 50, 100, 250 ms
SPlT
2-4
Input correction
IN-B
2-5
Input digital filter
)1 0.1 to 120.0 sec
MAvF
2-6
SV low limit value
-50 Within 2-1 Input specification
L-SV
2-7
SV high limit value
H-SV
1200
Control output
2-8
mode
O-FT
H-C
2-9
Control type
C-MD
pP
2-10 Control output 1
OUT1
2-11 Control output 2
CURR
OUT2
Control output 1
2-12
range
O!MA
4-20 4-20, 0-20 mA
Control output 2
2-13
range
O@MA
Heating control
2)0
2-14
cycle
H-T
@0
Cooling control
2)0
2-15
cycle
C-T
@0
AL1 alarm
2-16
operation
AM!A
□□□.■
AL-1
2-17 AL1 alarm option
2-18 AL1 Hysteresis
A!HY
AL2 alarm
2-19
operation
AL-2
AM!A
2-20 AL2 alarm option
2-21 AL2 hysteresis
A@HY
2-22 LBA time
01)
LBaT
2-23 LBA band
LBaB
Transmission
2-24
output1 mode
AoM1
PV
Transmission
2-25
output1 low limit
FS!L
-50
Transmission
2-26
output1 high limit
FS!H
1200
Transmission
2-27
output2 mode
AoM2
PV
Transmission
2-28
output2 low limit
FS!L
-50
Transmission
2-29
output2 high limit
FS!H
1200
2-30 Digital input key
DI-K
STOP
2-31 Sensor error, MV
ErMV
2-32 Screen protection
OFF OFF, 1, 30, 60 min
DSP
2-33 Comm. protocol
RTU RTU: Modbus RTU, ASCI: Modbus ASCII
PRCL
2-34 Comm. address
ADRS
2-35 Comm. speed
96 48, 96, 192, 384, 576, 1152 (×100) bps
BPS
2-36 Comm. parity bit
NONE None, Even, Odd
PRTY
2-37 Comm. stop bit
STP
2-38 Response time
20 5 to 99 ms
RSwT
2-39 Comm. write
EnA EN.A: Enable, DIS.A: Disable
COMW
2-40 Parameter reset
NO YES, NO
INIT
01) - Initialization condition of LBA time (alarm output status)
Alarm reset, change '2-8 Control output mode' (standard alarm: OFF, alarm latch: OFF),
Change '2-4 Input correction' or SV (Standard alarm: latch, alarm latch: latch),
Error status: OPEN, HHHH, LLLL (Standard alarm: Immediately ON, alarm latch: Immediately ON)
- Stop condition of LBA operation (Alarm output status)
Set '2-22/23 LBA time/band: 0' (standard alarm: OFF, alarm latch: latch)
Stop control output, execute auto tuning (standard alarm: OFF, alarm latch: latch),
If '2-1 Input specification' is changed, the settings are initialized.
02) After auto tuning, the range is set as twice of the integral time automatically. If the previous setting value is
outside of the range automatically set, it is set to the nearest Max. or Min. value of the range.
03) After auto tuning, the range is set as 10% of the proportion band automatically. If the previous setting value is
outside of the range automatically set, it is set to the nearest Max. or Min. value of the range.
0 -999 to 999 (-199.9 to 999.9) ℃/℉
L-SV ≤ H-SV - 1-digit ℃/℉
H-SV ≥ L-SV + 1-digit ℃/℉
HEAT: Heating, COOL: Cooling, H-C:
Heating&Cooling
PID, ONOF: ON/OFF, P.P: PID-PID*, ON.ON:
ON/OFF-ON/OFF*, P.ON: PID-ON/OFF*,
ON.P: ON/OFF-PID*
[Current/SSR output model]
SSR, CURR: Current
[Relay output model]
0.5 to 120.0 sec
[Current/SSR output model]
0.5 to 120.0 sec
[Relay output model]
0.5 to 120.0 sec
[Current/SSR output model]
0.5 to 120.0 sec
□□□
AM0: OFF
AM1: Deviation high limit alarm
AM2: Deviation low limit alarm
AM3: Deviation high, low limit alarm
AM4: Deviation high, low limit reserve
alarm
AM5: Absolute value high limit alarm
AM6: Absolute value low limit alarm
SBA: Sensor break alarm
LBA: Loop break alarm
HBA: Heater break alarm
■
A: Standard alarm, B: Alarm latch, C:
Standby sequence 1, D: Alarm latch and
sequence 1, E: Standby sequence 2, F:
Alarm latch and sequence 2
• Enter to option setting: Press [◀] key in
2-16 AL-1 alarm operation.
1 1 to 100 (0.1 to 50.0) ℃/℉
[Dual alarm output model]
Same as '2-16/17 AL1 alarm operation/
option'
[Dual alarm output model]
1 to 100 (0.1 to 50.0) ℃/℉
1
0 0 to 9999 sec or auto setting
02)
0 to 999 (0.0 to 999.9) ℃/℉ or Auto setting
03)
2
[Transmission output model]
PV, SV, H-MV: Heating MV), C-MV: Cooling
MV
[Transmission output model]
Refer to 'Input Type and Using Range'
[Dual transmission output model]
PV, SV, H-MV: Heating MV, C-MV: Cooling
MV
[Dual transmission output model]
Refer to 'Input Type and Using Range'
STOP: Stop control output, ALRE: Alarm
reset, AT: Auto tuning execution, OFF
0.0 (OFF) to 100.0 (ON)
0
-100 (Cooling ON) to 0.0 (OFF) to 100
(Heating ON)
1 1 to 99
2 1, 2 bit
Function: Alarm
Condition
-
-
88* 8
-
Alarm
Alarm
-
operation
option
-
■ Operation
-
-
Name
Alarm operation
-
-
-
* 2-8 Control
Deviation
output mode:
high limit
H-C
High deviation: Set as 10℃ High deviation: Set as -10℃
-
2-10/11 Control
Deviation
output 1/2:
low limit
CURR
Low deviation: Set as 10℃
-
2-10/11 Control
Deviation
output 1/2: SSR
high, low
limit
-
2-10/11 Control
output 1/2: SSR
Deviation
high, low
limit reverse
OFF
Absolute
-
value high
limit
Absolute value: Set as 90℃ Absolute value: Set as 110℃
Absolute
value low
limit
Absolute value: Set as 90℃ Absolute value: Set as 110℃
-
Sensor break -
Heater break -
2-16/17
Loop break
-
AL1/2 Alarm
operation: AM1
to AM6 or HBA
■ Option
2-8 Control
output mode:
Name
Description
HEAT or COOL
Standard
If it is an alarm condition, alarm output is ON. If it is a clear alarm
2-16/17
alarm
condition, alarm output is OFF.
AL1/2 Alarm
If it is an alarm condition, alarm output is ON and maintains ON
operation: AM1
Alarm latch
status.
to AM6 or HBA
First alarm condition is ignored and from second alarm
2-16/17
Standby
condition, standard alarm operates. When power is supplied
AL1/2 alarm
operation: LBA
sequence 1
and it is an alarm condition, this first alarm condition is ignored
and from the second alarm condition, standard alarm operates.
Alarm
If it is an alarm condition, it operates both alarm latch and
latch and
standby sequence. When power is supplied and it is an alarm
-
standby
condition, this first alarm condition is ignored and from the
sequence 1
second 1alarm condition, alarm latch operates.
First alarm condition is ignored and from second alarm
condition, standard alarm operates. When re-applied standby
Standby
sequence and if it is alarm condition, alarm output does
sequence 2
not turn ON. After clearing alarm condition, standard alarm
2-8 Control
operates.
output mode:
Basic operation is same as alarm latch and standby sequence1.
HEAT or COOL
Alarm
It operates not only by power ON/OFF, but also alarm set value,
latch and
or alarm option changing. When re-applied standby sequence
standby
and if it is alarm condition, alarm output does not turn ON.
sequence 2
-
After clearing alarm condition, alarm latch operates.
2-8 Control
output mode:
HEAT or COOL
2-8 Control
output mode:
H-C
-
-
-
-
-
-
-
-
-
Set both alarm operation and alarm option by combining.
Each alarm operates individually in two alarm output models.
When the current temperature is out of alarm range, alarm clears
automatically.
OFF
H
ON
OFF
H
ON
SV
PV
PV
SV
100℃
110℃
90℃
100℃
ON
H
OFF
ON
H
PV
SV
SV
PV
90℃
100℃
100℃
110℃
Low deviation: Set as -10℃
ON
H
OFF
H
ON
PV
SV
PV
90℃
100℃
110℃
High, Low deviation: Set as 10℃
OFF
H
ON
H
OFF
PV
SV
PV
90℃
100℃
110℃
High, Low deviation: Set as 10℃
H
ON
OFF
H
ON
PV
SV
SV
PV
90℃
100℃
100℃
110℃
ON
H
OFF
ON
H
PV
SV
SV
PV
100℃
110℃
90℃
100℃
• H: Alarm output hysteresis
Description
No alarm output
If deviation between PV and
SV as high-limit is higher
than set value of deviation
temperature, the alarm
output will be ON.
If deviation between PV
OFF
and SV as low limit is higher
than set value of deviation
temperature, the alarm
output will be ON.
If deviation between PV
and SV as high/low-limit
is higher than set value of
deviation temperature, the
alarm output will be ON.
If deviation between PV and
SV as high/low-limit is lower
than set value of deviation
temperature, the alarm
output will be OFF.
If PV is higher than the
absolute value, the output
will be ON.
OFF
If PV is lower than the
absolute value, the output
will be ON.
It will be ON when it detects
sensor disconnection.
It will be ON when it detects
heater disconnection.
It will be ON when it detects
loop disconnection.
Condition
of re-apply
-
-
Power ON
Power ON,
change SV,
change
alarm
temperature
/ operation
or change
STOP to RUN
mode