Autonics TR1D-T4CC Manual - Página 3

Navegue en línea o descargue pdf Manual para Controlador de temperatura Autonics TR1D-T4CC. Autonics TR1D-T4CC 6 páginas. Independent single display pid temperature controllers

Autonics TR1D-T4CC Manual
Input Type and Using Range
• The setting range of some parameters is limited when using the decimal point display.
Decimal
Display
Input type
point
Method
1
K (CA)
0.1
1
J (IC)
0.1
1
Thermo
L (IC)
-couple
0.1
1
T (CC)
0.1
R (PR)
1
S (PR)
1
1
DPt100
Ω
0.1
RTD
1
CU50
Ω
0.1
Nickel120
1
Ω
■ Display accuracy
• The setting range of some parameters is limited when using the decimal point display.
Using
Input type
temperature
At room
temperature
(23℃±5 ℃)
Thermocouple
RTD
Out of room
temperature
range
• When multiple products (or more) are mounted without separation, ±1°C is added to all accuracy.
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
22.5
Using range(℃)
Using range(℉)
-50 to 1,200
-58 to 2,192
KCaH
-50.0 to 999.9
-58.0 to 999.9
KCaL
-30 to 800
-22 to 1,472
JIcH
-30.0 to 800.0
-22.0 to 999.9
JIcL
-40 to 800
-40 to 1,472
LIcH
-40.0 to 800.0
-40.0 to 999.9
LIcL
-50 to 400
-58 to 752
TCcH
-50.0 to 400.0
-58.0 to 752.0
TCcL
0 to 1,700
32 to 3,092
RPR
0 to 1,700
32 to 3,092
5PR
-100 to 400
-148 to 752
DPtH
-100.0 to 400.0
-148.0 to 752.0
DPtL
-50 to 200
-58 to 392
CUsH
-50.0 to 200.0
-58.0 to 392.0
CU%L
-80 to 260
-112 to 500
NI12
Measurement accuracy
(PV ±0.3% or ±1 ℃ higher one) ±1-digit
• Thermocouple R (PR), S (PR) below 200 ℃:
(PV ±0.5% or ±3 ℃ higher one) ±1-digit,
Over 200 ℃:
(PV ±0.5% or ±2 ℃ higher one) ±1-digit,
• Thermocouple L (IC), RTD Cu50 Ω:
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
• Thermocouple R (PR) , S (PR):
(±1.0% or ±5 ℃ higher one) ±1-digit
• Thermocouple L (IC), RTD Cu50 Ω:
(PV ±0.5% or ±3 ℃ higher one) ± 1-digit
100
Connections
Back
AL1
SOURCE
5
6
7
8
OUT1
OUT2
SSR
SSR
Current
Current
mA
mA
1
2
3
4
Front
Relay
Relay
■ Terminal support by model
Terminal No. 1
2
3
4
5
Function
Control
Control
Alarm
output 1
output 2
output
Model
TR1D-14RN
Relay
-
Relay
TR1D-14RR
Relay
Relay
Relay
TR1D-R4RR
Relay
Relay
Relay
TR1D-T4RR
Relay
Relay
Relay
Current
TR1D-14CN
-
Relay
SSR
Current
Current
TR1D-14CC
Relay
SSR
SSR
Current
Current
TR1D-R4CC
Relay
SSR
SSR
Current
Current
TR1D-T4CC
Relay
SSR
SSR
Initial Display When Power is ON
When power is supplied, after all display will flash for a while, series and model name
are displayed sequentially. After input sensor type will flash twice, enter into RUN mode.
All display
Series
Model
****
TR1D
SV
℉ ℃
OUT1 OUT2 AL1
Errors
Display Description
Flashes if input sensor is disconnected or sensor is
not connected.
OPEN
HHHH Flashes when PV is higher than input range.
LLLL Flashes when PV is lower than input range.
Back
mA
Transmission
Current
transformer
Communication
CT
13
14
15
16
TC
B'
A
B
9
10
11
12
Front
6
7
8
9 10 11 12
13 14 15
Temperature
CT
Power -
sensor input
input
TC
-
-
-
RTD
TC
-
-
RTD
TC
-
-
RTD
TC
-
-
RTD
TC
-
-
-
RTD
TC
-
-
RTD
TC
-
-
RTD
TC
-
-
RTD
Input
Run mode
specification
T4RR
KCaH
Troubleshooting
Check input sensor status.
When input is within the rated
temperature range, this display
disappears.
output
output
RTD
16
Option
output
-
-
-
-
-
Trans
-mission
Communi
-cation
-
-
-
-
-
Trans
-mission
Communi
-cation
2^6
OUT1 OUT2 AL1