■ Program mode
Parameter
Display Default Setting range
Input
2-1
aMA2 Refer to 'Input Type and Using Range'.
specification
IN-P
Temperature
2-2
?C ℃, ℉
unit
UNIT
2-3
Display unit
?/O %, OFF, ℃, ℉
dUNT
Low limit
2-4
Input
L-RG
0$00
High limit
2-5
Input
H-RG
2)00
2-6
Decimal point
)0 0.0, 0.00, 0.000, 0
dP
2-7
Low limit scale
00)0 -19,999 to 19,999
L-SC
High limit
2-8
10)0 -19,999 to 19,999
scale
H-SC
4 mA output
2-9
scale
lOUT
00)0
20 mA output
2-10
scale
hOUT
10)0
Input and
transmission
2-11
output
ExI0
SP
extension
01)
AL1 alarm
2-12
operation
AT!A
□□□.■
AL-1
AL1 alarm
2-13
option
AL2 alarm
2-14
operation
AL2 alarm
AL-2
AT!A
2-15
option
AL3 alarm
2-16
operation
AL3 alarm
AL-3
AT@A
2-17
option
AL4 alarm
2-18
operation
AL4 alarm
AL-4
AT@A
2-19
option
Alarm output
2-20
001 001 to 999
hysteresis
A-HY
Input special
2-21
function
InSF
LIN
Input
2-22
0000 -999 to 999
correction
IN-B
Input digital
2-23
04 01 (OFF) to 16
filter
MAvF
Digital input
2-24
Terminal
DI-T
HOLD
Digital input
2-25
key
DI-K
HOLD
2-26 Display color
CLOR
RED
Alarm display
2-27
color
02)
C-AL
RRRR
Sensor break
2-28
alarm output
BURN
ON
Comm.
2-29
address
ADRR
01
2-30 Comm. speed
BAUD
(6K
2-31 Comm. write
COmY
EnA
2-32 Lock
LOC
OFF
01) Extension is not allowed below 0 mA and 0 V. ±1 V and 10 V Inputs cannot be set to 10P.
02) When alarm is cleared, or two alarms operate at the same time, the latest alarm's color is applied.
When error occurs during alarm, the set color of 'Display color' parameter is applied.
Within input range,
L-RG + 20% of F.S. ≤ H-RG
PV t
[
ransmission output model]
• Input: Thermocouple, RTD:
Within input range
• Input: Analog
L-SC ≤ L.OUT + 10% of F.S. ≤ H.OUT ≤
H-SC
PV t
[
ransmission output model]
Setting
Transmission
Input range
value
output range
0P
no extension
4 - 20 mA
5P
±5% extension 3.2 - 20.8 mA
10P
±10% extension 2.4 - 21.6 mA
[Alarm output model]
□□□
AT0: Off
AT1: Absolute high limit alarm
AT2: Absolute low limit alarm
SBA: Sensor break alarm
■
A: Standard alarm
B: Alarm latch
C: Standby
D: Alarm latch and
sequence
standby sequence
• Enter to option setting: Press [◀] key in
2-15 AL-1 alarm operation.
[Alarm output model]
Same as 2-12/13 AL1 alarm operation/
option
[4 alarm output model]
Same as 2-12/13 AL1 alarm operation/
option
LIN: Linear, ROOT: Root, SQAR: Square,
TUF: Two unit function
HOLD: Hold, ZERO: Zero-point adjustment,
AL.RE*: Alarm reset *[Alarm output model]
Setting
Display part Color
value
RUN mode
Error
RED
Red
Red
GRN
Green
Green
YELO
Yellow
Yellow
R--G
Red
Green
G--R
Green
Red
[Alarm output model]
Select each digit separately.
R: Red, G: Green, Y: Yellow
Display color when alarm is ON
AL-1: Green → Yellow
AL-2: Yellow → Red
AL-3: Red → Green
AL-4: Green → Red
[Transmission output model]
OFF: 4 mA - 5%, ON: 20 mA + 5%
[Communication output model]
01to99
[Communication output model]
1.2K: 1200, 2.4K: 2400, 4.8K: 4800,
9.6K: 9600, 19.2K: 19200 bps
[Communication output model]
EN.A: Enable, DIS.A: Disable
OFF
LOC1: Program mode lock (check only)
Monitoring mode unlock
LOC2: Checking and setting program mode
lock
Monitoring mode setting lock (check
only)
Communication Parameter Setting
Condition
■ Read Input Status (Func: 2, R/W: R)
-
Address
Parameter
2-1 Input
100001 (0000) AL1 indicator
specification:
Thermocouple,
100002 (0001) AL2 indicator
RTD
100003 (0002) AL3 indicator
100004 (0003) AL4 indicator
100005 (0004) ℉ indicator
2-1 Input
100006 (0005) ℃ indicator
specification:
Analog
100007 (0006) % indicator
■ Read Input Register (Func: 4, R/W: R)
Address
Parameter
300001 (0000) Present value
-
Input
300002 (0001)
specification
300003 (0002) Decimal point
2-1 Input
300004 (0003) PWM OUT
specification:
Analog
X (MSB)
% indicator
℃ indicator
℉ indicator
-
300005 (0004)
AL4 indicator
AL3 indicator
AL2 indicator
AL1 indicator
(LSB)
-
■ Program mode setting group (Func: 03/06/16, R/W: R/W)
Address
Parameter
-
400001 (0000) Input specification
400002 (0001) Temperature unit
400003 (0002) Display unit
400004 (0003) High limit Input
-
400005 (0004) Low limit Input
400006 (0005) High limit scale
400007 (0006) Low limit scale
400008 (0007) Input correction
2-12/14/16/18
AL-1/2/3/4
400009 (0008) Input digital filter
alarm
400010 (0009) AL1 alarm operation
operation: AT1,
AT2
400011 (000A) AL2 alarm operation
-
400012 (000B) AL3 alarm operation
400013 (000C) AL4 alarm operation
-
400014 (000D) AL1 alarm option
-
400015 (000E) AL2 alarm option
400016 (000F) AL3 alarm option
-
400017 (0010) AL4 alarm option
Alarm output
400018 (0011)
hysteresis
400019 (0012) 20 mA output scale
400020 (0013) 4 mA output scale
-
400021 (0014) Decimal point
Input and
400022 (0015)
transmission output
extension
400023 (0016) Digital input Terminal
400024 (0017) Digital input key
-
400025 (0018) Input special function
Sensor break alarm
400026 (0019)
output
-
400027 (001A) Lock
-
400028 (001B) Display color
400029 (001C) AL1 display color
-
400030 (001D) AL2 display color
400031 (001E) AL3 display color
400032 (001F) AL4 display color
400033 (0020) Comm. address
-
400034 (0021) Comm. speed
400035 (0022) Comm. write
• Func : Read Holding Register/Preset Single Register/Preset Multiple Register
Output range
0: OFF, 1: ON
Output range
-19999 ~ 19999
Refer to 'Input specification parameter
setting/output value'
0004H: .0000, 0003H: 0.000, 0002H: 0.00, 0001H:
0.0, 0000H: 0
0 ~ 20000
-
0: OFF, 1: ON
Display Setting range
Refer to 'Input specification
parameter setting/output value'
IN-P
UNIT 0: ℃, 1: ℉
dUNT 0: ℃, 1: ℉, 2: %, 3: OFF
Same as parameter setting range
H-RG
L-RG
Same as parameter setting range
H-SC
L-SC
IN-B Same as parameter setting range
MAvF Same as parameter setting range
1: Absolute high limit alarm
AL-1
2: Absolute low limit alarm
AL-2
3: Sensor break alarm
4: No alarm
AL-3
AL-4
AL-1 10: Standard alarm
11: Alarm latch
12: Standby sequence
AL-2
13: Alarm latch and standby
AL-3
sequence
AL-4
A-HY Same as parameter setting range
Same as parameter setting range
hOUT
lOUT
0004H: .0000, 0003H: 0.000,
0002H: 0.00, 0001H: 0.0, 0000H: 0
dP
ExI0 0: 0%, 1: 5%, 2: 10%
DI-T 0: Alarm reset, 1: Hold,
2: Zero-point adjustment
DI-K
0: Linear, 1: Root, 2: Square,
3: Two Unit Function
InSF
BURN 0: ON, 1: OFF
LOC 0: OFF, 1: LOCK1, 2: LOCK2
0: Red, 1: Green, 2: Yellow,
3: Red-Green, 4: Green-Red
CLOR
C-AL 0: Red, 1: Green, 2: Yellow
ADRR Same as parameter setting range
0: 192000, 1: 9600, 2: 4800,
3: 2400, 4: 1200
BAUD
COmY 0: Disable, 1: Enable
Condition
-
Condition
-
-
2-1 Input
specification:
Analog
-
-
-
Condition
Same
as each
parameter
setting
condition