IMPORTANT ENCODER INSTALLATION INFORMATION
Mounting the Encoder: The encoder should be mounted such that its shaft
is in close as possible alignment with the axis of the driving machine or
motor shaft.
CAUTION: The loads applied to the encoder shaft must be in
accordance with the specificatios of this device.
Important Wiring Instructions: Use of shielded cable is recommended for
all encoder installations. The shield should be connected to signal-ground
at the receiving device only.
Grounding: For applications with high ground potential differences,
DO NOT ground the encoder through both machine and controls end.
Connect the shield at the controls end only. NOTE: If the shield is
connected at both ends, grounding problems that degrade system
performance can result.
CE Grounding Measures – For best EMC immunity the cable screen
must be grounded on both encoder and controls end. For cable
lengths longer than 30m or outdoor applications, additional measures
must be implemented to comply with CE requirements. Connection of
the encoder to DC power supply network is prohibited if CE compli-
ance is required. CE-compliant products are tested to EN61326-1
EMC.
In all cases, system CE compliance is ultimately the responsibility of
the manufacturer integrating the encoder.
Connecting the shield at both ends can cause grounding problems
that degrade system performance.
If possible, run the encoder cable through a dedicated conduit (not shared
with other wiring). Use of conduit will protect the cable from physical
damage and provide a degree of electrical isolation. Do not run the cable
in close proximity to other conductors that carry current to heavy loads
such as motors, motor starters, contactors, solenoids, etc. This practice
can induce electrical transients in the encoder cable, potentially interfering
with reliable data transmission.
Refer to Electrical Connections table for wiring information. To avoid
possible damage, do not connect or disconnect the encoder connector or
wiring while power is applied to the system.
CAUTION: Unused encoder signal wires must be individually
insulated and under no circumstances be in contact with ground,
voltage sources, or other signal lines.