Autonics PSAN-L01CH Series Manual
Navegue en línea o descargue pdf Manual para Instrumentos de medida Autonics PSAN-L01CH Series. Autonics PSAN-L01CH Series 2 páginas. Small size, 1/2,000 resolution connector type digital pressure sensor
También para Autonics PSAN-L01CH Series: Manual (13 páginas)
DIGITAL PRESSURE SENSOR(Fluid type)
PSAN SERIES
M
A
N
U
Thank you very much for selecting Autonics products.
For your safety, please read the following before using.
Caution for your safety
※Please keep these instructions and review them before using this unit.
※Please observe the cautions that follow;
Warning
Serious injury may result if instructions are not followed.
Caution
Product may be damaged, or injury may result if instructions are not followed.
※The following is an explanation of the symbols used in the operation manual.
Caution: Injury or danger may occur under special conditions.
Warning
1. In case of using this unit with machinery(Ex: nuclear power control, medical equpment, ship, vehicle,
train, airplane, combustion apparatus, safety device, crime/disaster prevention equipment, etc) which
may cause damages to human life or property, it is required to install fail-safe device.
It may cause a fire, human injury or damage to property.
2. Do not use it in flammable gas because it does not have an explosion proof construction.
It may cause explosion.
Caution
1. This unit shall not be usde outdoors.
It might shorten the life cycle of the product or give an electric shock. This unit is proper indoor environmnet.
2. Do not apply the pressure beyond rated pressure.
It may cause damage to this unit.
3. Do not use it beyond power supply.
It may cause damage to this unit.
4. Do not make a short circuit for the load.
It may cause damage to this unit.
5. Do not wire incorrectly in power polarity etc.
It may cause damage to this unit.
6. Do not use corrosive gas or liquid as it is only for non-corrosive gas.
It may cause damage to this unit.
7. Do not give power to its case or twist its case strongly.
It may cause damage to this unit.
Dimensions
30
30
32
20
2-M3 Tap
PT 1/8"
(Standard)
Inside M5 Tap
17
※A: PT1/8" model(Standard): 8, NPT1/8" model: 8, 7/16"-20 UNF model: 11
※1: Only for PT1/8" model, NPT1/8" model
20
●Bracket A
1.6
20
2-M4 Bolt
45
30
20
35
●Bracket B
25
54
●Mounting bracket
40
23
. Panel cut-out
30
6
(Panel thickness 0.8mm to 3.5mm)
36
+0.5
0
※B: PT1/8" model(Standard): 56.3, NPT1/8" model: 56.3, 7/16"-20 UNF model: 59.3
Part descriptions
1. Range of rating pressure: It is possible to change the pressure unit in Pressure
1
sensor. Please use different unit as label for your application.
2
2. 4digit LED display(Red): Used to indicate measured pressure value, setting value
and error message.
3. Output1 indicator(Red): Output 1 is ON, LED will be ON.
4
3
4. Output2 indicator(Green): Output 2 is ON, LED will be ON.
5.
key: Used to enter into Preset/Parameter setting mode and to save Setting mode.
5
6.
,
key: Used to set parameter and preset, peak value check mode, function
setting or output operation mode.
+
key: Used for zero point adjustment function by pressing
6
1 sec. simultaneously in RUN mode.
Functions
Pressure unit change Function
PSAN-LV01C(P) and PSAN-LC01C(P) has 7 kinds of pressure unit, PSAN-L01C(P) and PSAN-L1C(P) has 5 kinds
of pressure unit. Please select the proper unit for application.
• PSAN-LV01C(P), PSAN-LC01C(P) : kPa, kgf/cm
2
, bar, psi, mmHg, inHg, mmH
• PSAN-L01C(P), PSAN-L1C(P) : MPa, kPa, kgf/cm
2
, bar, psi
※ When using mmH
O unit, please multiply display value by 100.
2
Output mode change Function
There are 5 kinds of control output mode in order to realize the various pressure detection.
• Hysteresis mode [ HYsM] : When needed to change hysteresis for detecting pressure.
• Window comparison output mode [ WIN] : When needed to detect pressure in certain area.
• Hysteresis - Window comparison output mode [ HY-W] : When both hysteresis mode and window comparison output
mode are required.
• Automatic sensitivity setting mode [ AUTO] : When needed to set detection sensitivity automatically at proper position.
• Forced output control mode [ fOUT] : When needed to display pressure with remaining comparison output OFF regardless
of setting value.
Control output change function
Type of control output for Out1 and Out2 can be able to set Normally Open and Normally Closed.
※ Note that Normally Open and Normally Closed provide opposite output.
Response time change function(Chattering prevention)
It can prevent chattering of control output by changing response time.
It is able to set 5kinds of response time(2.5ms, 5ms, 100ms, 500ms, 1000ms) and if the response time is getting
longer, the detection will be more stable by increasing the number of digital filter.
Analog output scale setting and Hold/Auto Shift setting function
• Analog voltage output scale setting: The scale function for analog output voltage (1-5VDC) is not fixed to the rated
pressure range. It can be changed for User's application. Analog output is 1-5VDC within the pressure range from
the pressure point(A-1V) for 1VDC to the pressure point (A-5V) for 5VDC.
• Analog current output scale setting: The scale for analog output Current (DC4-20mA) is not fixed to the rated pressure
range. It can be changed for User's application. Analog output is 4-20mA within the pressure range from the pressure
point (A-04) for 4mA to the pressure point (A-20) for 20mA.
• Hold/Auto Shift input setting
- Hold function: A function to hold PV and Control output while signal is input.
- Auto Shift function: A function to compensate the setting value for changed value of reference pressure as threshold
level if reference pressure of the device changes.
Key lock function
The key lock function prevents key operations so that conditions set in each mode. [preset/parameter mode are not
inadvertently changed. There are 2 kinds of key lock functions available.
• LOC1: All keys are locked; therefore it is not available to change parameter settings, preset value, zero adjustment,
High/Low peak check and SH.IN data initialization. (Lock setting change is available)
• LOC2: Partially locked status; therefore it is not available to change parameter settings only(Lock setting change is
available). Other settings are still available.
• OFF: All of the setting is available, all keys are unlocked.
Zero point adjustment function
The zero point adjustment function forcibly sets the pressure value to "Zero" when the pressure port is opened to
atmospheric pressure. When the zero adjustment is applied, analog output [Voltage or Current] is changed by this
function.(Press
+
keys over 1 sec. in RUN mode.)
High Peak / Low Peak Hold Function
This function is to diagnosis malfunction of the system caused by parasitic pressure or to check through memorizing
the max./min. pressure occurred from the system.
Error
Error display
Description
Countermeasures
When external pressure is input while adjusting zero
ERR1
Try again after removing external pressure.
point.
ERR2
When overload is applied on control output
Remove overload.
When setting condition is not met in Auto sensitivity
Check setting conditions and set proper setting
ERR3
setting mode.
values.
When applied pressure exceeds Low-limit of display
LLLL
pressure range.
Apply pressure within display pressure range.
When applied pressure exceeds High-limit of display
HHHH
pressure range.
-HH-
Set the corrected setting value within setting
Auto shift correction error.
-LL-
pressure range.
-HL-
※The above specifications are subject to change without notice.
Specifications
Pressure type
Voltage output
Current output
Hold/Auto shift input
A
L
Rated pressure range
Display pressure range
Min.display unit
Max. pressure range
Applied fluid
Power supply
Current consumption
Control output
※2
Hysteresis
Repeat error
Response time
Short circuit protection Built-in
Voltage output
Analog
output
※3
Current output
Display method
Resolution
Pressure unit
MPa
kPa
kgf/cm
2
bar
psi
mmHg
inHg
mmH₂O
Display accuracy
Dielectric strength
Insulation resistance
Vibration
Ambient temperature -10 to 50℃, storage : -20 to 60℃
Environ-
ment
Ambient humidity 30 to 80%RH, storage :30 to 80%RH
Protection
Material
Cable
Approval
Weight
※1: (P) is PNP output type,
(unit:mm)
R1/8: PT1/8"model(Standard), NPT1/8: NPT1/8"model(Option)
7/16-20UNF: 7/16"-20 UNF model(Option)
※2: In hysteresis output mode, detection difference is variable.
●Accessory
※3: It is allowed to select one analog output type only.
. Pressure unit label
※
: Resolution(1000/2000) of min. Display interval is automatically selected
4
depend on pressure units.
※
: This weight is with packaging and the weight in parentheses is only unit weight.
5
Output operation mode
※1
※ PSAN series has 5 kinds of output operation mode, please use proper output operation mode in accordance
with detection.
Hysteresis mode[ HYS.M]
. Bracket A
. Bracket B
It is able to set certain value for pressure detection
level(ST1, ST2) and hysteresis(HYS1, HYS2).
Pressure
. Connector cable (PSO-C01, 2m)
ST2
HYS2
ST1
HYS1
●Option
2-M4 Bolt
OUT1 N.O.
ST1/ HYS1
. Front protection
OUT1 N.C.
ST1/ HYS1
cover(PSO-P01)
OUT2 N.O.
ST2/ HYS2
OUT2 N.C.
ST2/ HYS2
Hysteresis-window comparison output mode[ HY-W]
①It is available to set hysteresis mode(ST1, HYS1)
and window comparison output mode when both
. Mounting bracket
hysteresis mode and window comparison output
mode(LOW, HIGH) are necessary.
(PSO-B02)
②Detection hysteresis is fixed to min. display range.
Pressure
※1
HIGH
※1
LOW
ST1
HYS1
OUT1 N.O.
ST1/ HYS1
OUT1 N.C.
ST1/ HYS1
OUT2 N.O.
LOW/ HIGH
OUT2 N.C.
LOW/ HIGH
+
keys over
Forced output control mode[ fOUT]
①Used to display pressure with forcibly holding comparing output OFF regardless of setting value.
②In parameter setting, if output operation mode setting OUtN is changed to fOUT, forced output control mode is operated.
③OUT1, 2 can be ON/OFF manually by pressing
RUN mode
O
2
fOUT
Flashing
in turn
RUN mode
Input/Output circuit and diagram
Analog output type (Voltage output PSAN-L
● NPN open collector output type
Over current
protection
circuit
Over current
protection
circuit
1kΩ
※
: For voltage output type only.
Hold / Auto Shift input type (PSAN-L
● NPN open collector output type
Over current
protection
circuit
Over current
protection
circuit
Installation
1.Pressure port is divided as basic and option specification.
Therefore, be sure that to use commercially available one touch
fitting. (Standard: R(PT)1/8", Option: NPT1/8", 7/16" - 20 UNF)
2.Please connect it by using spanner(17 mm ) at the metal part in
order not to overload on the body when connecting one touch
fitting.
3.Two different fixing brackets are provided for PSAN model.
Select proper one with considering your application environments.
4.At first, please unscrew hexagon wrench bolt and assemble
the bracket on this unit by fixing hexagon the wrenchbolt. In
this case, tightening torque of hexagon wrench should be max.
30kgf . cm. It may cause mechanical problems.
Gauge pressure
Negative pressure
Standard pressure
PSAN-LV01C(P)V-
PSAN-L01C(P)V-
PSAN-L1C(P)V-
PSAN-LV01C(P)A-
PSAN-L01C(P)A-
PSAN-L1C(P)A-
PSAN-LV01C(P)H-
PSAN-L01C(P)H-
PSAN-L1C(P)H-
0.0 to -101.3kPa
0.0 to 100.0kPa
0 to 1,000kPa
5.0 to -101.3kPa
-5.0 to 110.0kPa
-50 to 1,100kPa
0.1kPa
0.1kPa
1kPa
2 times of rated
2 times of rated
1.5 times of rated
pressure
pressure
pressure
Air, Non-corrosive gas and fluid that will not corrode SUS316L
12V-24VDC ±10%(ripple P-P:Max. 10%)
Max. 50mA(Analog Current Output type Max 75mA)
NPN or PNP open collector output
• Load voltage: Max. 30VDC • Load current: Max. 100mA
• Residual voltage - NPN: Max. 1V, PNP: Max. 2V
Min. display range
±0.2%F.S. ± Min. display range
Selectable 2.5ms, 5ms, 100ms, 500ms, 1000ms
• Output voltage: 1-5VDC ±2% F.S. • Linear: Max. ±1% F.S.
• Output impedance: 1kΩ
• Zero point: Max. 1VDC ±2% F.S. • Span: Max. 4VDC ±2% F.S. • Response time: 50ms
• Resolution: Automatically changed to 1/1000 or 1/2000 by pressure unit
• Output current: DC4-20mA ±2% • Linear: Max. ±1% F.S.
• Response time:70ms
• Zero-point: Max. DC4mA ±2% F.S. • Span: Max. DC16mA ±2% F.S.
• Resolution: Automatically changed to 1/1000 or 1/2000 by pressure unit
7segment LED Display
1000
2000
1000
2000
1000
2000
-
-
0.001
-
0.001
-
0.1
-
0.1
-
1
-
0.001
-
0.001
-
0.01
-
0.001
-
0.001
-
0.01
-
-
0.01
-
0.01
-
0.1
-
0.4
-
0.02
0.1
-
0℃ to 50℃ : Max. ±0.5% F.S., -10 to 0℃ : Max. ±1% F.S.
1000VAC 50/60Hz for 1 minute
Min. 50MΩ(at 500VDC megger)
1.5mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z direction for 2 hours
IP40(IEC specification)
Front case: PC, Rear case: PA6, Pressure port: SUS316L
Connector cable (Ø4, 5-wire, Length: 2m)
(AWG24, Core diameter : 0.08mm, Number of cores : 40, Insulator out diameter: Ø1mm)
Approx. 173g(Approx. 88g)
※F.S.: Rated pressure.
of model name is as pressure port.
※There may be ±1digit error in hysteresis
by pressure unit calculation error.
※Environment resistance is rated at no
freezing or condensation.
Window comparison output mode[ WIN]
①It is able to set the range for high(HI-1, HI-2)/
low(LO-1, LO-2)limit of pressure detection level when
it is required to detect pressure at a certain range.
②Detection hysteresis is fixed to min. display range.
Pressure
※1
HI-2
※1
LO-2
※1
HI-1
※1
LO-1
Time
OUT1 N.O.
LO-1/ HI-1
Time
OUT1 N.C.
LO-1/ HI-1
Time
OUT2 N.O.
LO-2/ HI-2
Time
OUT2 N.C.
LO-2/ HI-2
Time
Automatic sensitivity setting mode[ AUTO]
①This function is to set pressure detection level to the
proper position automatically. It is set by applied
pressure from two positions(ST1, ST2).
②Detection hysteresis is fixed to min. display range.
③The pressure detection level(SET) is shown in the
following calculation.
(ST1+ST2)
SET=
Pressure
※ 1: Min. display range
※1
ST2
SET=(ST1+ST2)/2
SET
※1
ST1
※1
Time
OUT1 N.O.
SET
Time
OUT1 N.C.
SET
Time
OUT2 N.O.
ST1/ ST2
Time
OUT2 N.C.
ST1/ ST2
Time
,
key While the forced output control mode is applied.
RUN mode
Forced output control mode
operation status
Current pressure
ON
8#1
OUT1
OFF
ON
OUT2
OFF
□□□□
□
□□□□
V-
, Current output PSAN-L
A-
● PNP open collector output type
(Brown)+V
(Brown)+V
Over current
Load
(Black)OUT1
protection
circuit
(Black)OUT1
Load
(White)OUT2
Over current
protection
circuit
12-24VDC
(White)OUT2
(Orange)
(Orange)
Analog output
Analog output
1kΩ
voltage/current
voltage/current
(Blue)0V
(Blue)0V
※
: For voltage output type only.
□□□□
□)
H-
● PNP open collector output type
(Brown)+V
(Brown)+V
Over current
(Black)OUT1
Load
protection
circuit
(Black)OUT1
Load
Over current
(White)OUT2
protection
circuit
12-24VDC
(White)OUT2
(Orange)Hold/
(Orange)Hold/
Auto shift input
Auto shift input
(Blue)0V
(Blue)0V
Caution
The tightening torque of one touch
fitting should be max. 100kgf . cm.
17mm
Spanner
It may cause machanical problems.
5.Bracket(PSO-B02) and front protection cover(PSO-P01)
are optional to sell.
Please see the figure for installation.
Spring washer
Protection
cover
(PSO-P01)
Hexagon wrench bolt
(M3×6)
Bracket panel
Setting
Press
key
Parameter
Pressure
over 3sec.
setting
unit setting
Compound pressure
Preset value
PSAN-LC01C(P)V-
Detection level 1 setting (out1)
setting
PSAN-LC01C(P)A-
Press
key
The forced output control mode is applied with pressign
Forced output
PSAN-LC01C(P)H-
control mode
in output operation mode(OUtM) parameter. For more detailed information, refer to '● Forced output control
setting
mode' '
Output operation mode'
-101.3kPa to 100.0kPa
Press
key
-101.3kPa to 110.0kPa
High peak
Peak hold
over 3sec.
value check
0.1kPa
2 times of rated
Press
Zero-point
Zero-point adjustment
pressure
keys over 1sec.
adjustment
Parameter setting
※ If the key lock is set (lock1 or lock2), unlock the key lock before setting parameters.
※ Press
,
key to change setting values.
※ Press
key to save setting value in each parameter and move to next parameters.
※ When pressing
key for 3 sec in the middle of parameter setting, current setting value will be saved in
EEPROM and [ RUN] will flash twice, then returned to RUN mode.
RUN mode
Press
key
Press
key
over 3sec.
over 3sec.
(MPa)
Pressure unit
MPA
UNIT
flashing
(mmH
O)
in turn
2
H2O
1000
2000
Window
Output operation
Hysteresis
comparison
-
-
mode
mode
output mode
-
0.1
OUtM
HYsM
-
0.001
flashing
in turn
-
0.001
-
0.02
Output
-
0.8
NoNC
1O2O
1O2C
-
0.03
flashing
in turn
-
0.1
Response time
SPD
@5
flashing
in turn
Analog voltage output
Analog current output
□□□□
□
(PSAN-L
V-
)
(PSAN-L
1V Scale
4mA Scale
※1
※1
A-1V
)0
A-04
flashing
in turn
5V Scale
20mA Scale
※2
A-5V
10)0
※2
A-20
flashing
in turn
※1: Setting range : Min.rated pressure ≤ [ A-1V, A-04] ≤ 90% of rated pressure
※2: Setting range : [ A-1V, A-04] + 10% of rated pressure ≤ [ A-SV, A-20] ≤ Max.rated pressure
Key lock
LOCK
OFF
flashing
in turn
※ If there is no additional key operation within 60 sec. while setting, current setting value is not valid and previous setting value
will be remained.
Preset Setting
※ [
] flashes twice when returning to RUN mode.
RUN
※ 1: Min. display range
※ Press
,
key to change setting values.
※ Press
key to save setting value in each parameter and move to next parameters.
Hysteresis mode
RUN mode
Pressure detection
Time
※Setting range :
level 1
Min.display pressure
ST1
2)0
< [ ST1] ≤ Max. display
Time
flashing
pressure
in turn
Time
Hysteresis level 1
※Setting range :
Min. display pressure
HYS1
1)0
Time
≤ [ HYS1] < [ ST1]
flashing
in turn
Time
Pressure detection
※Setting range :
level 2
Min.display pressure
ST2
4)0
< [ ST2] ≤ Max. display
flashing
pressure
in turn
Hysteresis level 2
※Setting range :
Min.display pressure
HYS2
3)0
≤ [ HYS2] < [ ST2]
flashing
in turn
2
※ 1: Min. display range
Window comparison output mode
RUN mode
Low-limit value of
※Setting range :
Pressure detection level 1
Min.display pressure
LO-1
1)0
≤ [ LO-1] ≤ Max. display
Time
pressure - (3×Min.display
flashing
in turn
interval)
Time
High-limit value of
※Setting range :
Pressure detection level 1
Time
[ LO-1] + (3×Min.display
HI-1
2)0
interval) ≤ [ HI-1]
flashing
≤ Max. display pressure
Time
in turn
Low-limit value of
※Setting range
Time
Pressure detection level 2
Min.display pressure≤
LO-2
3)0
[ LO-2] ≤ Max. display
pressure-(3×Min. display
flashing
in turn
interval)
High-limit value of
※Setting range
Pressure detection level 2
[ LO-2]+(3×Min. display
HI-2
4)0
interval) ≤ [ HI-2]
RUN mode
flashing
≤ Max. display pressure
in turn
Hysteresis-Window comparison output mode
Time
RUN mode
Time
※Setting range
Pressure detection
level 1
Min. display pressure
< [ ST1] ≤ Max. display
ST1
1)0
pressure
flashing
in turn
□
)
※Setting range
Hysteresis level 1
Min. display pressure
HYS1
2)0
≤ [ HYS1] < [ ST1]
flashing
in turn
※Setting range
12-24VDC
Low-limit value of
Pressure detection level 2
Min. display pressure
≤ [ LOW] ≤ Max. display
LOW
3)0
Load
pressure - (3×Min. display
flashing
interval)
in turn
High-limit value of
※Setting range
Pressure detection level 2
Load
[ LOW] + (3×Min. display
HIGH
4)0
interval) ≤ [ HIGH]
flashing
≤ Max. display pressure
in turn
Zero point adjustment
1.Please press
+
keys for over 1sec. at the same time
putting an applied pressure in state of the atmospheric
pressure.
2.When the zero point adjustment is completed, it will
display )0 and return to RUN mode automatically.
※If executing zero point adjustment on external pressure
being at pressure port ERR1 flashes 5times. Please
12-24VDC
execute it in the atmospheric pressure after removing
external pressure.
※Please execute zero point adjustment regularly.
Load
Caution for using
Load
1. Do not insert any sharp or pointed object into pressure port.
It may cause malfunction and damage the sensor.
2. Be sure that this unit must avoid direct touch with water, oil, thinner etc.
3. It is ready to operate 3 sec. after it is turned ON. Be sure not to use the product within 3 sec.
4. When using switching mode power supply, frame ground (F.G.) terminal of power supply
should be grounded.
5. To avoid inductive noise, keep the wiring away from power line, high voltage line.
It may cause malfunction.
6. When moving this unit from warm place to cold place, please remove the humidity on the
cover then use it.
7. Do not press the setting button with sharp or pointed object.
8. Do not apply a tensile strength in excess of 30N to the cables or connector.
9. When using mmH
O unit, please multiply display value by 100.
2
10.Installation environment
① It shall be used indoor.
② Altitude Max. 2,000m
③ Pollution Degree 2
④ Installation Category II
※It may cause malfunction if above instructions are not followed.
Major products
Panel bracket
Proximity sensors
Photoelectric sensors
(PSO-B02)
Fiber optic sensors
Door/Door side sensors
Counter
Timers
Display units
Power controllers
Body
Panel meters
Graphic/Logic panels
(PSAN)
Temperature controllers
Tachometer/Pulse(Rate) meters
Temperature/Humidity transducers
Stepping moters/drivers/motion controllers
Laser marking system (CO
, ND:YAG)
2
Laser welding/soldering system
Output operation
Output
Response
Analog output scale and
Key lock
mode setting
type setting
time setting
setting
Hold/Auto Shift input setting
Detection level 2 setting (out2)
key after selecting forced output control mode(fOUT)
Low peak
Auto shift input setting
value check
(In case of Hold/Auto shift input type model)
※In case of using mmH
O unit,
2
(KPa)
(kgf/cm
)
(bar)
2
multiply 100 by display value.
KPA
KGF
BAR
※In case of standard pressure
type model, [ MPA], [ KPA], [ KGF],
(inHg)
(mmHg)
(psi)
[ BAR], [ PSI] parameters are
INHG
MMHG
PSI
displayed only.
Hysteresis-Window
Auto sensitivity
Forced output
comparison output
setting mode
control mode
mode
WIN
HY-W
AUTO
fOUT
Parameter OUT1 output
OUT2 output
Normally Open
Normally Open
1O2O
1C2O
1C2C
Normally Open
Normally Closed
1O2C
1C2O
Normally Closed Normally Open
Normally Closed Normally Closed
1C2C
%0
100
500
1000
※Unit: ms
Hold/Shift input
□□□□
□
□□□□
□
(PSAN-L
H-
)
A-
)
External input function
)0
D-IN
HOLD
SHFT
flashing
flashing
in turn
in turn
Select Hold(Refer to " Function")
Control output for
Auto shift function
10)0
ShOT
OUT1
OUT2
flashing
flashing
ALL
in turn
in turn
※See setting
Function
key lock function for more
LOC1
LOC2
detailes.
Automatic sensitivity setting mode
RUN mode
Pressure detection
※Min.display pressure
level 1
≤ [ ST1] ≤Max. display
ST1
1)0
pressure - 1% of rated
flashing
pressure
in turn
Pressure detection
※[ ST1]+1% of rated
level 2
pressure≤ [ ST2] ≤
ST2
2)0
Max. display pressure
flashing
in turn
Auto setting value
※[ SET]
= ([ ST1]+[ ST2])/2
STT
1%0
※Press
,
key for
flashing
manual adjustment
in turn
※ [ ERR3] Error flashes 3 times in case setting
conditions are not met, resetting is on standby.
※If there is no additional key operation within 60 sec. while setting,
it is returned to Run mode (Except for force output mode).
Previous set values are remained.
※In case of changing output operation mode, no preset values
will be initialized. Instead, previous output operation settings will
become the preset values.
※When changing pressure display unit, resolution and Hold/Auto
Shift input function, preset values will be initialized as shown the
table below. (When changing pressure display unit, preset value
will be automatically switched to changed pressure unit.)
< Preset Default >
(unit: kPa)
Negative
Standard
Standard
Compound
Output
pressure
pressure
pressure
pressure
mode
0.0 to -101.3
0.0 to 100.0
0 to 1,000
-101.3 to 100.0
ST1:-50.0
ST1:50.0
ST1:500
ST1:50.0
HYS1:0.0
HYS1:0.0
HYS1:0
HYS1:-50.0
HYS.M
ST2:-50.0
ST2:50.0
ST2:500
ST2:50.0
HYS2:0.0
HYS2:0.0
HYS2:0
HYS2:-50.0
LO-1:0.0
LO-1:0.0
LO-1:0
LO-1:-50.0
HI-1:-50.0
HI-1:50.0
HI-1:500
HI-1:50.0
WIN
LO-2:0.0
LO-2:0.0
LO-2:0
LO-2:-50.0
HI-2:-50.0
HI-2:50.0
HI-2:500
HI-2:50.0
ST1:-50.0
ST1:50.0
ST1:500
ST1:50.0
HYS1:0.0
HYS1:0.0
HYS1:0
HYS1:-50.0
HY-W
LOW:0.0
LOW:0.0
LOW:500
LOW:-50.0
HIGH:-50.0
HIGH:50.0
HIGH:0
HIGH:50.0
ST1:0.0
ST1:0.0
ST1:0
ST1:-50.0
AUTO
ST2:-50.0
ST2:50.0
ST2:500
ST2:50.0
SET:-25.0
SET:25.0
SET:250
SET:0.0
※When using the forced output function, Hold/Auto shiftfunction is
not available to use in Hold/Auto shift mode.
Peak Hold / Auto Shift Check/Change
RUN mode
Press
key over 3sec.
High Peak value
hPEK
10)6
flashing
in turn
Low Peak value
lPEK
-@7
flashing
in turn
Reference pressure
for Auto Shift
※1
ShIN
5)0
flashing
in turn
※1: PSAN-L
H -
Displayed only when D-IN is set
to SHFT. Auto shift reference pressure can be set within
display error range.(Low_Range ≤ SH.IN ≤ High_Range)
• Low_Range = Min.display pressure - Min. preset setting value
• High_Range = Max.display pressure - Max. preset setting value
※If pressing
+
keys for over 1sec. in case of High peak
/ Low peak/ Auto shift reference pressure value, setting value
will be erase and return to next operation.
※ [ RUN] flashes twice, then return to RUN mode.
Switching
mode Power
Supply
Ground
http://www.autonics.com
Area sensors
Pressure sensors
Satisfiable Partner For Factory Automation
Rotary encoders
HEAD QUARTERS :
Sensor controllers
116, Ungbigongdan-gil, Yangsan-si, Gyeongsangnam-do, Korea
OVERSEAS SALES :
#402-404, Bucheon Techno Park, 655, Pyeongcheon-ro,
Wonmi-gu, Bucheon, Gyeonggi-do, Korea
TEL:82-32-610-2730 / FAX:82-32-329-0728
E-mail : [email protected]
The proposal of a product improvement
and development : [email protected]
EP-KE-77-0019E