Autonics ADIO-EC Manual del producto - Página 4

Navegue en línea o descargue pdf Manual del producto para Sistemas de E/S Autonics ADIO-EC. Autonics ADIO-EC 8 páginas. Remote i/o boxes

Autonics ADIO-EC Manual del producto

Unit Descriptions

1 2
4
5
6
7
2
01. Grounding hole
02. Mounting hole
03. Insertion part
for the name plate
3
4
5
8
9
04. Ethernet port
05. Power supply port
06. PDCT port
07. I/O port
08. Status indicator
09. I/O port indicator

Installation

■ Mounting
01. Prepare a flat or metal panel in the enclosure.
02. Drill a hole to mount and ground the product on the surface.
03. Turn off all power.
04. Fix the product using M4 screws in the mounting holes.
Tightening torque: 1.5 N m
M4
■ Grounding
᜸ Be sure to use a cable with low impedance and as short as possible for
connecting the housing to the product.
01. Connect the grounding strap and M4×10 screw with washer.
02. Fix the screw in the grounding hole.
Tightening torque: 1.2 N m
M4