AutoPulse 4100-3113AR Manual de instrucciones de instalación - Página 7

Navegue en línea o descargue pdf Manual de instrucciones de instalación para Unidad de control AutoPulse 4100-3113AR. AutoPulse 4100-3113AR 10 páginas. Idnet 2 sprinkler card and idnet loop card

4100-3113AR IDNet 2 Sprinkler Card, and 4100-3111 IDNet Loop Card Installation Instructions
Class A / DCLA wiring
To wire the loop terminals as a Class A circuit, complete the following steps:
1.
Set the jumper assigned to the loop to the A position, see Figure 10.
-
Loop A = Jumper P1 on the Sprinkler Card
-
Loop B = Jumper P2 on the Sprinkler Card
-
Loop C = Jumper P1 on the first IDNet Loop card
-
Loop D = Jumper P1 on the second IDNet Loop card
2.
Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield to prevent it coming in contact with other
components.
3.
Route the wiring from the primary terminals (B+, B-) to the corresponding inputs on the first device.
4.
Route the wiring from the first device to the next device as in/out. See
5.
Route the wiring from the last device to the panel.
6.
Connect the wiring to the corresponding secondary terminals (A+, A-).
Class A wiring notes:
• If there are remote isolators or isolator bases on the loops, you must begin addressing the devices on the B side and assign each successive
isolator a higher address than the isolator that it precedes.
• If there are no remote isolators or isolator bases on the loops, you can assign the device addresses in any sequence.
Class B / DCLB wiring
When wiring the loop for Class B circuits, both the B+, B- and A+, A- terminals are available for parallel connections. In the IDNet circuitry, A+ is
connected to B+, and A- is connected to B- so circuits can stem from either one. In addition, two wires can be connected to each screw terminal.
To wire the loop terminals as a Class B circuit, complete the following steps:
1.
Set the jumper assigned to the loop to the B position, see Figure 12.
-
Loop 1 = Jumper P1 on the sprinkler card
-
Loop 2 = Jumper P2 on the sprinkler card
-
Loop 3 = Jumper P1 on the left IDNet Loop Card
page 7
Figure 10: Class A jumper setting
Figure
6. Repeat this step for each device.
Figure 11: IDNet loop Class A wiring
579-1214AR Rev. B