Notes:
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
If other cable types are used, operating distances and performance may be reduced
depending on the cable quality.
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to function correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.
3
Distance between proximity readers
The distance separating any two proximity readers must not be less than 200 mm (8 in) in all directions.
200 mm
When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of
the wall is not less than 200 mm (8 inches) away.