2iB SC10 Manual de instalación y uso - Página 12

Navegue en línea o descargue pdf Manual de instalación y uso para Controlador 2iB SC10. 2iB SC10 16 páginas. Single pump controller
También para 2iB SC10: Manual de inicio rápido (5 páginas)

2iB SC10 Manual de instalación y uso
12.
Reference
DIP Switches
Current Range
SW
1
2
Off
Off
Off
On
On
Off
On
On
Pump Run Time Target
SW
3
4
Off
Off
Off
Off
Off
On
Off
On
On
Off
On
Off
On
On
On
On
Alarm Relay Activates for ...
SW
Setting
6
AIN (CT) Fault
7
Stop / Low Float
8
Start / High Float
9
Fail to Run (Low Current)
On = Activates for this condition. Default= Off,Off,Off,Off
Stop / Low Float Invert
SW
10
Setting
Off
Closed = Low (default)
On
Open = Low
Current Window (%)
SW
Setting
11
On: +16%
12
On: +8%
13
On: +4%
14
On: +2%
Default = Off,Off,Off,On.
Modes
SW
Setting
15
On: Disable Snore Stop
16
On: Disable Timer Start
Current % Display
PA = PAUSING. Pump is Pausing.
CL = CLEANING. Pumps is Stopped for a Cleaning flush.
Number = The measured current as a percentage of the
measured range (taking into account the Current Transformer
range configured using the DIP switches as per section 5.1).
12
Setting
100% (default)
50%
25%
12.5%
5
Setting
Off
3 min
On
5 min (default)
Off
8 min
On
15 min
Off
30 min
On
1 h
Off
2 h
On
4 h
Default = Off,Off
Terminals
Power
DC+ / AC
24VAC
DC- / AC (Earth)
12-24VDC
Earth
Pump Run Relay
Alarm Relay
Pump Current
-
CT (4-20mA)
+
Digital Inputs
DIN Common
DIN 1: Start / High Float
DIN 2: Stop / Low Float
DIN 3: Up Pushbutton
DIN 4: Down Pushbutton
DIN 5: Set Pushbutton
DIN 8: Remote Config. Mode
No Connection
Do not use (AIN+ Loop Power)
Modbus RTU
A
(RS485)
B
Earth
No Connection
LED Indicators
Power
On
Power is Present
Flash
Unit starting up.
Run / Pause
On
Pump is Running
Pulse
Pump is Pausing and will start when
Flash
pause timer completes or high float
or start signal activates.
Fast
Pump Snoring. Pump will stop after
Flash
10 seconds of snoring
Slow
Pump Starting or running a cleaning
Flash
cycle.
Stop Input /
On
Stop Input / Lo Float Active
Low Float
Start Input /
On
Start Input / Hi Float Active
High Float
Alarm
Flash
Alarm Present & Alarm Relay Active
Fail to Run
On
Pump previously failed to run.
(Current Not detected when the
pump run relay is active.)
Fast
Pump is failing to run.
Flash
Hi Current
Fast
CT input too high
Flash
Pulse
CT input is above 100% of range.
Flash
Consider adjusting CT measuring
range or using a larger CT.
Lo Current
Fast
CT input too low.
Flash
Pulse Flash = Active for 0.25 secs every second.
Slow Flash = 1Hz Flash. Fast Flash = 2 Hz Flash.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
18
19-27
28
29
30
31
32-36