Emerson 203-5751 Hoja de información del producto
Navegue en línea o descargue pdf Hoja de información del producto para Accesorios Emerson 203-5751. Emerson 203-5751 3 páginas. Wall-mounted rh sensor and rh/temperature sensor
También para Emerson 203-5751: Manual de instalación (6 páginas)
Wall-Mounted RH Sensor and RH/Temperature Sensor
Wall-Mounted RH Sensor and RH/Temperature Sensor
Overview
CPC specs a wall-mounted relative humidity (RH)
sensor (P/N 203-5751) and/or RH and temperature
sensor (P/N 203-5752) for use in building control and
anti-sweat control applications using CPC input
boards.
Specifications
General
Input Power
12VDC
Enclosure
High-impact plastic, white
Relative Humidity (RH)
Sensing
Digitally profiled thin-film
Element
capacitive
RH Accuracy
±3% RH over the range 20%-90%
RH
Stability
<0.5% RH per year
Operating
0-100% RH
Humidity Range
Analog Output
0-5VDC; 3-wire, observe
polarity
Scaling
0-100% RH
Temperature
Temperature
±0.4°F from 32°F to 140°F
Accuracy
Analog Out
Resistive, 2-wire, no polarity
Choosing a Mounting
Location
Mount the sensor indoors in a central location within
the zone to be measured, away from doors, windows,
vents, heaters, and outside walls that could affect
temperature readings. The sensor should be at least
four feet from the floor, and no higher than necessary
to prevent tampering.
Product Information Sheet
Product Information Sheet
Mounting
29
1. Insert a screwdriver into the gap in the plastic
on the bottom side of the sensor enclosure,
and pry the front part of the enclosure away
from the rear mounting plate. Pull the front
away from the mounting plate until the top
separates from the mounting plate.
2. Remove the punch outs above the wiring
connectors so that the sensor cables can be
run into the sensor enclosure (see Figure 1).
3. Use the pre-made holes to mount the plate
on a junction box using the screws provided,
or mount it against a wall or riser. Do not
mount the plate upside down or sideways.
The plate should be mounted with the
terminal blocks toward the bottom.
4. If necessary, drill or cut a hole in the wall to
allow the sensor cable to be run through the
wall into the sensor's terminal block.
Figure 1 - RH/Temp Sensor Back Plate
203-5751