Emerson Network Power M221S Manual del usuario - Página 6
Navegue en línea o descargue pdf Manual del usuario para Controlador Emerson Network Power M221S. Emerson Network Power M221S 20 páginas.
![Emerson Network Power M221S Manual del usuario](/uploads/products/server2/1985209/1985209.jpg)
2
Chapter 1 Introduction
1.2 Technical Specifications
1.2.1 Operating Conditions
Input voltage
Operating temperature range
(ambient temperature)
Storage temperature
Relative humidity
Elevation
*: The LCD display may become difficult to display at the temperature above 50C or below -10C, and user may
need to adjust contrast of the LCD at these temperatures for easy reading.
1.2.2 EMC Requirements
Item
Radiated Emission
EMI
Conducted Emission
Immunity to ESD
Immunity to Radiated
Magnetic Field
Immunity to EFT
EMS
Immunity to Surge
Immunity to Conducted
Magnetic Field
1.2.3 RoHS Compliance
Complies with RoHS R6 standard.
1.2.4 Safety Requirement:
CE,UL: Certification by third party.
1.2.5 Protective Level
IP20
1.2.6 Mechanical Data
Dimensions: 202 × 86.8 × 42 (mm, excluding golden finger),
211.5 × 86.6 × 42 (mm, including golden finger)
Table 1-2 Operating Conditions
Item
Test Item
Standard
EN55022
EN55022
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
LCU+ Series Controller User Manual
19V ~ 60V
-10 C ~ +55 C*
-40 C ~ +75 C
≤ 90%RH
≤ 3000m
Table 1-3 EMC Requirements
Requirement
Class B
Class B
8kV contact discharge,
15kV air discharge
10V/m, 80MHz-1GHz
1.4 - 2 GHz
2kV for DC Power Input
Port, 1kV for
Communication Port
800V Common Mode for
DC Power Port, 12ohm
Internal Resistance; 500V
Differential Mode, 2ohm
Internal Resistance; 1kV
for Signal Port, Common
Mode, 42ohm Internal
Resistance
10Vrms
Range
Criterion
Remarks
--
--
--
--
To enclosure, RS232,
A
Ethernet Port, LCD
Panel, and Keys
A
--
CAN, RS232,
B
Ethernet
Communication Port
Signal Ports include
B
CAN, RS232,
Ethernet
Power Supply, CAN,
A
RS232, Ethernet