Galvin Engineering CliniMix Lead Safe 100.00.71.00 Manual de instalación del producto - Página 14
Navegue en línea o descargue pdf Manual de instalación del producto para Productos de fontanería Galvin Engineering CliniMix Lead Safe 100.00.71.00. Galvin Engineering CliniMix Lead Safe 100.00.71.00 18 páginas. Hob mounted thermostatic progressive basin mixer - lever
5. Disinfection Process
−
Turn the tap handle anti-clockwise fully.
−
Hot water will now pass thru the cold inlet and into the thermostatic mixing chamber (exiting the mixed outlet).
−
Run water for the correct disinfection time as shown in Table 4.
Temperature
Disinfection
Time
60 degrees
30 Minutes
Celsius
65 degrees
15 Minutes
Celsius
70 degrees
10 Minutes
Celsius
Table 4 - G
uide to disinfection temperatures v/s time
To avoid scalding/burning, keep clear of the mixed outlet.
6. Cool Down Unit
This unit becomes very hot during operation. Extreme care should be taken when reversing hoses.
Ensure the unit is cool to touch before reassembly.
− After the required disinfection time, turn the tap handle to the off position.
− Repeat steps 1 to 3 and return the hoses to their original position.
− Check tap for correct operation.
14
st
Version 2.1, 31
July 2020 , 14 of 18