AGS Merlin 1000S+i Manual de uso e instalación - Página 5
Navegue en línea o descargue pdf Manual de uso e instalación para Controlador AGS Merlin 1000S+i. AGS Merlin 1000S+i 9 páginas. Gas & electric utility controller
Merlin 1000S+i
Gas & Electric Utility Controller
2.9
12VDC [9]
This is a permanent 12v DC output when there is power at the panel and can be used to
create a relay switch with the BMS relay output.
Please contact your supplier for further information.
2.10
INTERNAL BUZZER
Operates at 65dB measured 30cm from closed panel.
2.11
PANEL TIMEOUT FACILITY
The panel has a built-in Auto-shut down feature and it will turn itself off after a predefined time.
Auto-shut down timeout is selectable.
There are two Dip-Switches located on the inside facia labelled [Time1] and [Time2].
The gas supply will be cut off at desired time-out.
To select required timeout – configure Dip Switches as follows;
2 HOURS (FACTORY SET)
Time1 Off / Time2 Off
4 HOURS
Time1 On / Time2 Off
8 HOURS
Time1 Off / Time2 On
NO TIMEOUT
Time1 On / Time2 On (auto-shut down disabled)
3
OPERATION
3.1
SYSTEM ON & OFF
1) Turn the key switch to ON position.
2) Gas & Electric LEDs will flash for *10 seconds.
3) Press the relevant service button to turn required utility on.
4) Turn the key switch to the OFF position to turn the panel off.
3.2
LED STATUS
POWER
When the system is connected to the mains supply, the Red LED of the AGS Logo located in
the bottom right corner of the panel will illuminate. When no power is present, this LED will not
light up.
RED = OK
OFF = No power to panel, a loose ribbon connection or the fuse may not be intact.
GAS ON
When the key switch is turned on, the gas valve will open and the green 'Gas On' LED will
illuminate.
GREEN = Gas On
OFF = Gas Off
Rev: 04 Date: 22-10-18
User & Installation Manual
5