IMPORTANT
Shut off gas supply before removing an existing range
and leave it off until new installation is completed.
Use only pipe joint compound that is approved for use
with petroleum gases. Install a manual shut-off valve
in an accessible location in the gas piping, external to
the range for the purpose of turning on or shutting off
gas to the range. To facilitate in moving or servicing
the range, a flexible connector complying with
ANSIZ21.69 is recommended.
• The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig (3.5 kPa). Check incoming
gas supply pressure and the manifold pressure
(after the regulator) using a manometer. The re-
quired manifold pressure for natural gas is 5" wa-
ter column and for LP is 10" W.C. The gas supply
line must be at least 1" W.C. above the manifold
pressure and must not exceed 14" W.C. (3.5 kPa or
1/2 psig)
1/2" PIPE NIPPLE
RESTRAINING DEVICE
Check for gas leaks using soap-water solution. Do not use open flame to check for leaks.

GAS CONNECTION:

GAS SHUT-OFF VALVE
QUICK DISCONNECT
8
Installation of this range must conform with local codes.
Call the local gas supplier for the applicable codes in
the area. If there are no codes, the installation must
conform with the NATIONAL FUEL GAS CODE ANSI
Z223.1 - Latest Edition. A copy of this code may be
obtained by contacting:
CSA America
8501 E. Pleasant Valley Rd.
Cleveland, Ohio 44131
(216) 524-4990
www.csa-america.org
The maximum allowable incoming gas pressure for
the regulator installed in the range is 1/2 psig (pounds
per square inch gauge), equivalent to 14 inches water
column. For LP-installation, a step down regulator must
be used to bring down the gas pressure from the LP
bottle to below 14 inches. The minimum incoming gas
pressure to the regulator must be 1 inch above the
range designed manifold pressure. Refer to chart on
gas conversion for the gas pressures.
GAS SUPPLY
FLEXIBLE HOSE