10.2. HYDRAULIC CONNECTION
It is very important for the water connections to be installed with care by qualified personnel.
03
Connect the unit to the hydraulic system with the indicated inlet/outlet connections. Make sure the connections are air tight with a sealant.
All heat exchangers (including the additional one) are equipped with an air vent near the top connection and a water drain near the lower
connection.
04
1" per 3ft
Coils can be partially drained; it is recommended to bleed air inside the coil to be drained completely.
Setting up the condensate drain:
The condensation drainage system must be set up with an adequate inclination to make sure the water drains properly.
05
The condensate drain system must be set up with an adequate p-trap in order to prevent the infiltration of odours.
Always install a plug for cleaning in the lower part of the p-trap in order to allow quick disassembly.
Position the drain pipes without mechanical stress on the drain connection of the unit.
Wall
1" per 3ft
Wall